Product Model
ELR H5-IES-PT/500AC-9-IOL

Selling Points
- 1Reverses 3~ AC motors up to 500 V AC and 9 A output current.
- 2Adjustable overload shutdown for enhanced motor protection.
- 3Emergency stop function up to SIL 3/PL e for safety.
- 4Push-in connection for easy installation.
- 5Connection to IO-Link for network integration.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Notes on operation | If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board. | Product type | Hybrid motor starters |
Product family | CONTACTRON | Operating mode | 100% operating factor |
Article revision | 06 | Number of phases | 3 |
Motor starter type | Reversing starter | Switching frequency | ≤ 2 Hz (Load-dependent) |
Switching frequency | ≤ 2 Hz (Load-dependent) | Maximum power dissipation | 7 W |
Minimum power dissipation | 0.88 W | Coordination type | 1 |
Rated control circuit supply voltage U | 24 V DC | Control supply voltage range | 19.2 V DC ... 30 V DC |
Rated control supply current I | 65 mA | Protective circuit | Surge protection
Reverse polarity protection; Parallel polarity protection diode |
Nominal voltage for I/O supply | 24 V DC (This supply voltage is provided via the IO-Link interface of the IO-Link master.) | Current consumption | typ. 65 mA ±15 % (24 V DC)
max. 150 mA |
Protective circuit | Reverse polarity protection
Short-circuit protection
Overload protection | Rated insulation voltage | 550 V |
Rated surge voltage | 6 kV | Overvoltage category | III |
Degree of pollution | 2 | Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) |
Isolation characteristics between the control input and control supply voltage to auxiliary circuit | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC | Operate threshold | > 60 A |
Response time | < 0.5 s | Input name | Enable input |
Rated actuating voltage U | 24 V DC | Triggering voltage range | 19.2 V DC ... 30 V DC |
Rated actuating current I | 7 mA | Switching threshold | 9.6 V (“0” signal)
19.2 V (“1” signal) |
Switching level | < 5 V DC (For EMERGENCY STOP) | Typical turn-off time | < 30 ms |
Number of ports | 1 | Connection method | COMBICON |
Connection technology | 3-conductor | Specification | V1.1.1 |
Reverse polarity protection | yes | Cycle Time | 30 ms |
Amount of process data | 8 Byte (Input data)
2 Byte (Output data) | Rated operating voltage U | 500 V AC |
Operating voltage range | 42 V AC ... 550 V AC | Rated operating current I | 9 A (AC-51)
7 A (AC-53a) |
Mains frequency | 50/60 Hz | Load current range | 1.5 A ... 9 A (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A | Cooling time | 20 min (for auto reset) |
Leakage current | 0 mA | Protective circuit | Surge protection; Varistor |
Connection method | Push-in connection | Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 | Connection method | Push-in connection |
Stripping length | 10 mm | Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | Conductor cross section AWG | 24 ... 14 |
Status display | LED (yellow) | Operating voltage display | Green LED |
Error indication | Red LED | Width | 22.5 mm |
Height | 127 mm | Depth | 114 mm |
Flammability rating according to UL 94 | V0 (Housing) | Degree of protection | IP20 |
Ambient temperature (operation) | -5 °C ... 55 °C (observe derating) | Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m | Certificate | UKCA-compliant |
Certificate | NLDX.E228652
NRNT.E172140 | Identification | ≤ 3 |
Note | Safe shutdown | Identification | e |
Note | Safe shutdown | Identification | ≤ 3 |
Note | Safe shutdown | SCCR | 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) |
FLA | 7.6 A (480 V AC) | Group installation | 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded) |
Category code | NLDX / NRNT | Horsepower ratings | 2 hp (208 V AC)
2 hp (230 V AC)
2 hp (240 V AC)
5 hp (480 V AC) |
Standards/regulations | IEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849 | Mounting type | DIN rail mounting |
Assembly note | alignable, for spacing see derating | Mounting position | vertical (horizontal DIN rail, motor output below) |
Specifications may be subject to change without notice