Product Model
ELR H5-I-PT- 24DC/500AC-9

Selling Points
- 1Reversible operation for flexible motor control.
- 2Compatible with 3-phase AC motors up to 500V AC.
- 3Adjustable overload shutdown for enhanced safety.
- 424V DC control voltage for precise operation.
- 5Push-in connection for easy installation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Notes on operation | If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board. | Product type | Hybrid motor starters |
Product family | CONTACTRON | Operating mode | 100% operating factor |
Article revision | 05 | Number of phases | 3 |
Motor starter type | Reversing starter | Switching frequency | ≤ 2 Hz (Load-dependent) |
Maximum power dissipation for nominal condition | 13.5 W | Switching frequency | ≤ 2 Hz (Load-dependent) |
Maximum power dissipation | 14.6 W | Minimum power dissipation | 1.1 W |
Coordination type | 1 | Rated control circuit supply voltage U | 24 V DC |
Control supply voltage range | 19.2 V DC ... 30 V DC | Rated control supply current I | 40 mA |
Protective circuit | Surge protection
Reverse polarity protection | Rated insulation voltage | 500 V |
Rated surge voltage | 6 kV | Overvoltage category | III |
Degree of pollution | 2 | Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC (e.g., 230/400 V AC, 277/480 V AC)
Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC |
Isolation characteristics between the control input and control supply voltage to auxiliary circuit | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC | Operate threshold | > 45 A |
Response time | 2 s | Input name | Control input right/left |
Rated actuating voltage U | 24 V DC | Triggering voltage range | 19.2 V DC ... 30 V DC |
Rated actuating current I | 5 mA (Input type 1) | Switching threshold | 9.6 V (“0” signal)
19.2 V (“1” signal) |
Typical turn-off time | < 30 ms | Protective circuit | Reverse polarity protection |
Rated operating voltage U | 500 V AC | Operating voltage range | 42 V AC ... 550 V AC |
Rated operating current I | 9 A (AC-51)
6.5 A (AC-53a) | Mains frequency | 50/60 Hz |
Load current range | 1.5 A ... 9 A (see to derating) | Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
Cooling time | 20 min (for auto reset) | Leakage current | 0 mA |
Protective circuit | Surge protection | Note | Confirmation: floating change-over contact, signal contact |
Contact switching type | 1 changeover contact | Switching capacity in accordance with IEC 60947-5-1 | 3 A (230 V, AC15)
2 A (24 V, DC13) |
Connection method | Push-in connection | Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 | Connection method | Push-in connection |
Stripping length | 10 mm | Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | Conductor cross section AWG | 24 ... 14 |
Status display | LED (yellow) | Operating voltage display | Green LED |
Error indication | Red LED | Width | 22.5 mm |
Height | 107.5 mm | Depth | 114 mm |
Flammability rating according to UL 94 | V0 (Housing) | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (observe derating) | Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m | Certificate | UKCA-compliant |
Certificate | NLDX.E228652 | SCCR | 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (500 V AC (fuse: 20 A RK5 (standard fault))) |
FLA | 6.5 A (500 V AC) | Group installation | 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded) |
Category code | NLDX / NRNT | Standards/regulations | IEC 60947-1
IEC 60947-4-2 |
Mounting type | DIN rail mounting | Assembly note | alignable, for spacing see derating |
Mounting position | vertical (horizontal DIN rail, motor output below) |
Specifications may be subject to change without notice