Product Model

ELR H5-I-PT-SWD/500AC-06

In Stock
Last updated: 2025/4/19
Phoenix Contact ELR H5-I-PT-SWD/500AC-06

Selling Points

  • 1Networkable Hybrid Motor Starter: Ideal for reversing 3-phase AC motors up to 500 V AC.
  • 2Adjustable Overload Shutdown: Ensures safe operation with customizable overload protection.
  • 3Emergency Stop Functionality: Provides immediate shutdown in emergency situations.
  • 4DIN Rail Mounting: Compact design for easy installation on DIN rails.
  • 5Push-in Connection: Simplifies wiring with secure push-in connections.
Product Details
ELR H5-I-PT-SWD/500AC-06
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Notes on operation
If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board.
Product type
Hybrid motor starters
Operating mode
100% operating factor
Article revision
04
Number of phases
3
Switching frequency
≤ 2 Hz (Load-dependent)
Maximum power dissipation for nominal condition
0.5 W
Switching frequency
≤ 2 Hz (Load-dependent)
Maximum power dissipation
2.5 W
Minimum power dissipation
0.88 W
Coordination type
1
Rated control circuit supply voltage U
24 V DC
Control supply voltage range
19.2 V DC ... 30 V DC
Rated control supply current I
60 mA
Protective circuit
Surge protection Reverse polarity protection; Parallel polarity protection diode
Rated insulation voltage
550 V
Rated surge voltage
6 kV
Overvoltage category
III
Degree of pollution
2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
Safe isolation (IEC 60947-1)
Isolation characteristics between the control input and control supply voltage to auxiliary circuit
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Operate threshold
> 10 A
Response time
< 0.5 s
Rated operating voltage U
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Rated operating current I
0.6 A (AC-51) 0.6 A (AC-53a)
Mains frequency
50/60 Hz
Load current range
75 mA ... 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2
Class 10
Cooling time
20 min (for auto reset)
Leakage current
0 mA
Protective circuit
Surge protection; Varistor
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Status display
LED (yellow)
Operating voltage display
Green LED
Error indication
Red LED
Width
22.5 mm
Height
107.5 mm
Depth
114 mm
Flammability rating according to UL 94
V0 (Housing)
Degree of protection
IP20
Ambient temperature (operation)
-5 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m
Certificate
NLDX.E228652 NRNT.E172140
SCCR
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) 5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA
0.6 A (480 V AC)
Group installation
20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded) 30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category code
NLDX / NRNT
Horsepower ratings
-
Standards/regulations
IEC 60947-1 EN 60947-4-2
Mounting type
DIN rail mounting
Assembly note
alignable, for spacing see derating
Mounting position
vertical (horizontal DIN rail, motor output below)

Specifications may be subject to change without notice