Product Model

ELR H5-I-SC- 24DC/500AC-0,6-SP

In Stock
Last updated: 2025/4/22
Phoenix Contact ELR H5-I-SC- 24DC/500AC-0,6-SP

Selling Points

  • 1Space-saving design: 22.5 mm wide for compact installations.
  • 2Long service life: Designed for extended operational periods.
  • 3Adjustable overload shutdown: Ensures motor safety and reliability.
  • 4Surge protection: Safeguards against electrical surges and spikes.
  • 5DIN rail mounting: Easy installation on vertical or horizontal DIN rails.
Product Details
ELR H5-I-SC- 24DC/500AC-0,6-SP
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Hybrid motor starters
Product family
CONTACTRON
Operating mode
100% operating factor
Insulation
safe isolation
Overvoltage category
III
Pollution degree
2
Number of phases
3
Service life electrical
3x 10
Maximum power dissipation for nominal condition
1.5 W
Reversing frequency
≤ 2 Hz
Maximum power dissipation
1.5 W
Minimum power dissipation
1.1 W
Coordination type
1
Rated insulation voltage
500 V
Rated surge voltage
6 kV
Rated control circuit supply voltage U
24 V DC
Control supply voltage range
19.2 V DC ... 30 V DC
Rated control supply current I
40 mA
Protective circuit
Surge protection Reverse polarity protection
Rated actuating voltage U
24 V DC
Triggering voltage range
19.2 V DC ... 30 V DC
Rated actuating current I
5 mA (Input type 1)
Switching threshold
9.6 V (“0” signal) 19.2 V (“1” signal)
Typical turn-off time
< 30 ms
Rated operating voltage U
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Rated operating current I
0.6 A (AC-51) 0.6 A (AC-53a)
Mains frequency
50/60 Hz
Load current range
75 mA ... 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2
Class 10A
Cooling time
20 min (for auto reset)
Leakage current
0 mA
Residual voltage
< 0.2 V
Protective circuit
Surge protection
Note
Confirmation: floating change-over contact, signal contact
Contact switching type
1 changeover contact
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Status display
LED (yellow)
Operating voltage display
Green LED
Error indication
Red LED
Width
22.5 mm
Height
107 mm
Depth
114 mm
Flammability rating according to UL 94
V0 (Housing)
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Certificate
NLDX.E228652
SCCR
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) 5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA
0.6 A (480 V)
Standards/regulations
DIN EN 50178
Standards/regulations
IEC 60947-4-2
Mounting type
DIN rail mounting
Assembly note
can be aligned with spacing: see derating
Mounting position
Vertical (horizontal DIN rail)

Specifications may be subject to change without notice