Product Model

ELR W3- 24DC/500AC- 9

In Stock
Last updated: 2025/4/17
Phoenix Contact ELR W3- 24DC/500AC- 9

Selling Points

  • 1Highly Reliable Operation: Built with a zero voltage switch and optional thermal fuse for stable performance.
  • 2Versatile Applications: Suitable for hybrid motor starters with reversing function and current monitoring.
  • 3Advanced Safety Features: Includes protection against polarity reversal, surge protection, and integrated locking circuit.
  • 4Efficient Design: Low power dissipation (0.88 W / 4.1 W) and high switching frequency.
  • 5Easy Installation: Compatible with DIN rail mounting and easy to align with spacing = 20 mm.
Product Details
ELR W3- 24DC/500AC- 9
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Solid-state contactor
Operating mode
100% operating factor
Article revision
08
Number of phases
3
Switching frequency
max. 5 Hz
Test voltage (Input/output)
5 kV
Switching frequency
max. 5 Hz
Reversing frequency
≤ 10 Hz
Rated insulation voltage
500 V
Rated surge voltage
6 kV
Overvoltage category
III
Degree of pollution
2
Insulation characteristics between the control input voltage to the main circuit
Basic insulation
Input name
Control input right/left
Rated actuating voltage U
24 V DC
Triggering voltage range
19.2 V DC ... 30 V DC
Voltage range with reference to U
0.8 ... 1.25 0.8 ... 1.25
Rated actuating current I
12.7 mA
Switching threshold
9.6 V (“0” signal) 19.2 V (“1” signal)
Protective circuit
Reverse polarity protection; Suppressor diode Surge protection
Error indication
Red LED
Status display
LED (yellow)
Rated operating voltage U
500 V AC
Operating voltage range
48 V AC ... 575 V AC
Rated operating current at AC-51
9 A
Rated operating current at AC-53a
9 A
Peak offstate voltage
1200 V
Mains frequency
40 Hz ... 100 Hz
Load current range
100 mA ... 9 A (see to derating)
Leakage current
6 mA
Residual voltage
< 1.5 V
Surge current
300 A (t = 10 ms)
Max. load value
580 A
Protective circuit
RCV circuit
Surge voltage protection
> 575 V AC
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm 5 lb
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm 5 lb
Status display
LED (yellow)
Error indication
Red LED
Width
67.5 mm
Height
99 mm
Depth
114.5 mm
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Certificate
UKCA-compliant
Certificate
NMFT.E323771
SCCR
5 kA (20 A RK5 (standard fault) fuse)
Standards/regulations
DIN EN 50178 EN 60947
Mounting type
DIN rail mounting
Assembly note
Can be aligned with spacing = 20 mm
Mounting position
Vertical (horizontal DIN rail)

Specifications may be subject to change without notice