Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Electronic motor manager
Operating mode
100% operating factor
Number of phases
3
Mains type
3-phase
Test voltage input/output
2.5 kV
Reversing frequency
≤ 2.5 Hz (at cos φ = 0.5)
Input name
Device supply
Nominal supply voltage
24 V DC
Supply voltage range with reference to U
0.8 ... 1.2
Quiescent current
80 mA AC
Protective circuit
Reverse polarity protection; Series polarity protection diode Surge protection
Operating voltage display
Green LED
Error indication
Red LED
Status display
LED (yellow)
Input name
Control input right/left
Nominal input voltage U
24 V DC
Input voltage range in reference to U
0.8 ... 1.2 0.8 ... 1.2
Typical input current at U
7 mA
Reaction time in normal load operation
< 35 ms
Typical response time
< 25 ms
Typical turn-off time
< 25 ms
Reaction time in normal load operation
< 35 ms
Switch-over frequency
< 2.5 Hz (at cos φ = 0.5)
Basic accuracy
± 2 % (Of end value, typ. ± 1%)
Current range
0.25 A ... 8 A
Measuring via
Current transformer for any conductor current
Nominal output voltage
500 V AC
Nominal output voltage range
110 V AC ... 550 V AC
Peak offstate voltage
1500 V
Mains frequency
50 Hz 60 Hz
Load current range
150 mA ... 8 A (see to derating)
Leakage current
typ. 7 mA
Residual voltage
typ. 1.4 V
Surge current
360 A (tp = 10 ms, at 25 °C)
Max. load value
645 A
Protective circuit
RC element; RC element Surge protection
Surge voltage protection
> 880 V
Number of outputs
4
Nominal output voltage
U
Continuous load current
max. 50 mA
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 6 mm²
Conductor cross section flexible
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 10
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 6 mm²
Conductor cross section flexible
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 10
Interface
RS-232
Transmission speed
4800 bit
Width
62 mm
Height
94 mm
Depth
122 mm
Color
green (RAL 6021)
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Standards/regulations
DIN EN 50178 safe isolation
Standards/regulations
DWR 1300/ZXX01/DD/7080.8d
Standards/regulations
EN 61000-6-2 EN 61000-6-4
Assembly note
Can be aligned with > 20 mm spacing
Mounting position
Vertical (horizontal DIN rail)

Specifications may be subject to change without notice