Product Model

FLK 24/EZ-DR/4000/KONFEK/S

In Stock
Last updated: 2025/4/21
Phoenix Contact FLK 24/EZ-DR/4000/KONFEK/S

Selling Points

  • 1Ensures reliable signal transmission with a braided shield.
  • 2Ideal for extended connections in industrial settings.
  • 3Supports multiple connections with ease.
  • 4Operates between -10°C to 70°C for flexible installations.
  • 5Meets special requirements in process technology and engineering.
Product Details
FLK 24/EZ-DR/4000/KONFEK/S
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
System cable
Insulation
Functional insulation
Overvoltage category
II
Pollution degree
2
Degree of protection
IP00
Degree of protection (Installation location)
≥ IP54 (Installation location)
Ambient temperature (operation)
-40 °C ... 70 °C (fixed installation) -10 °C ... 70 °C (flexible installation)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m
Max. permissible operating voltage
25 V AC 60 V DC
Nominal operating mode
100% operating factor
Max. current carrying capacity per path
1 A
Rated insulation voltage
63 V
Rated surge voltage
0.6 kV (1.2/50 μs)
Cable length
40 m
UL AWM Style
2464/1061
Number of positions
40
Shielded
yes
Cable type
40X0.14 [PVC]
Conductor type
Assembled shielded round cable
Conductor structure signal line
7x 0.16 mm
AWG signal line
26
Conductor cross section
40x 0.14 mm²
Wire diameter incl. insulation
1 mm ±0.03 mm
External cable diameter
9.80 mm ±0.3 mm
Outer sheath, material
Semi-rigid PVC
External sheath, color
gray
Conductor material
Tin-plated Cu litz wires
Cable resistance
≤ 145 Ω/km (at 20 °C)
Insulation resistance
≥ 20 MΩ*km (20 °C)
Smallest bending radius, fixed installation
101 mm
Smallest bending radius, movable installation
182 mm
Dynamic load capacity (bending)
Max. bending cycles: 5000 (at a radius of ≥ 18x outside diameter)
Halogen-free
no
Flame resistance
IEC 60332-1-2 (raw cable) VDE 0842, Part 332-1-2 (raw cable) IEC 60332-3-22 (raw cable) UL VW-1 CSA FT-1
Resistance to oil
can withstand occasional splashes (raw cable)
Cable type
Cable for one module
Connection in acc. with standard
IEC 60603-13
Connection method
IDC/FLK socket strip
Number of connections
1
Number of positions
24
Note
The braided shield is routed to a separate cable end. The separate cable end is approximately 0.5 m long (H05V-K 1 mm², black)
Insertion/withdrawal cycles
> 50
Pitch
2.54 mm
Connection in acc. with standard
IEC 60603-13
Connection method
IDC/FLK socket strip
Number of connections
1
Number of positions
24
Insertion/withdrawal cycles
> 50
Pitch
2.54 mm
Standards/regulations
DIN EN 50178
Notes on operation
For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.

Specifications may be subject to change without notice