Product Model
FLK 50-PA/EZ-DR/KS/5000/YUC

Selling Points
- 1Highly Compatible with Yokogawa Controllers: Designed for seamless integration with Yokogawa CS3000, CentumVP, and ProSafe-RS controllers.
- 250-Position Socket Strip: Injection-molded on both sides for secure and efficient connections.
- 350m Cable Length: Provides ample reach for various industrial applications.
- 4IEC 60603-13 Compliant: Meets international standards for reliable electrical connections.
- 5UL and UKCA Approvals: Ensures safety and compliance with global regulations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Front adapter | Article revision | 06 |
Operating voltage (DC) | ≤ 30 V DC | Nominal operating mode | 100% operating factor |
Current (Per path) | ≤ 500 mA (uncoiled) | Suitable I/O card | ADV151
ADV551 |
Suitable I/O card | NFDV151
NFDV551 | Suitable I/O card | SDV541
SDV144
SDV521 |
Connection in acc. with standard | IEC 60603-13 (in compliance) | Connection method | Yokogawa, I/O cards compatible |
Number of connections | 1 | Number of positions | 50 |
Tightening torque | 0.5 Nm (Screw connection) | Insertion/withdrawal cycles | > 50 |
Pitch | 2.54 mm | Connection in acc. with standard | IEC 60603-13 (in compliance) |
Connection method | Yokogawa, KS compatible | Number of connections | 1 |
Number of positions | 50 | Tightening torque | 0.5 Nm (Screw connection) |
Insertion/withdrawal cycles | > 50 | Pitch | 2.54 mm |
Length | 50 m | UL AWM Style | 2464/1061 |
Number of positions | 50 | Shielded | yes |
Cable type | 50X0.14 [PVC] | Conductor type | Assembled shielded round cable |
Conductor structure signal line | 7x 0.16 mm | AWG signal line | 26 |
Conductor cross section | 50x 0.14 mm² | Wire diameter incl. insulation | 1 mm ±0.03 mm |
External cable diameter | 11.00 mm ±0.3 mm | Outer sheath, material | Semi-rigid PVC |
External sheath, color | gray | Conductor material | Tin-plated Cu litz wires |
Cable resistance | ≤ 145 Ω/km (at 20 °C) | Insulation resistance | ≥ 20 MΩ*km (20 °C) |
Smallest bending radius, fixed installation | 114 mm | Smallest bending radius, movable installation | 205 mm |
Dynamic load capacity (bending) | Max. bending cycles: 5000 (at a radius of ≥ 18x outside diameter) | Halogen-free | no |
Flame resistance | IEC 60332-1-2 (raw cable)
VDE 0842, Part 332-1-2 (raw cable)
IEC 60332-3-22 (raw cable)
UL VW-1
CSA FT-1 | Resistance to oil | can withstand occasional splashes (raw cable) |
Degree of protection | IP20 | Degree of protection (Installation location) | ≥ IP54 (Installation location) |
Ambient temperature (operation) | -40 °C ... 70 °C (fixed installation)
-10 °C ... 70 °C (flexible installation) | Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m | Certificate | UKCA-compliant |
Mounting position | any | Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Specifications may be subject to change without notice