Product Model
FLKM-2FLK14/HF/S7

Selling Points
- 1High Compatibility: Compatible with Siemens SIMATIC S7-300 and ET 200 M controllers.
- 2Flexible Connections: Supports up to 16 channels with SIMATIC-specific marking and 18 additional connection terminal blocks.
- 3Robust Design: Functional insulation ensures reliable operation in various industrial environments.
- 4Wide Operating Range: Operates within -20°C to 50°C ambient temperature and up to 2000 meters altitude.
- 5Compliance and Safety: Meets overvoltage category II and pollution degree 2 standards, ensuring safe and reliable operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Interface module | Insulation | Functional insulation |
Overvoltage category | II | Pollution degree | 2 |
Nominal voltage U | ≤ 25 V AC
≤ 60 V DC | Max. current carrying capacity per branch | 1 A |
Rated insulation voltage | 63 V | Rated surge voltage | 0.6 kV (1.2/50 μs) |
Connection in acc. with standard | IEC 60603-13 | Connection method | FLK14 pin strip |
Number of positions | 14 | Connection method | Screw connection |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 | Width | 56.5 mm |
Height | 77 mm | Depth | 57.5 mm |
Degree of protection | IP00 | Degree of protection (Installation location) | ≥ IP54 (Installation location) |
Ambient temperature (operation) | -20 °C ... 50 °C | Altitude | max. 2000 m |
Standards/regulations | DIN EN 50178: 1998-04 | Standard designation | Air clearances and creepage distances |
Mounting type | DIN rail mounting | Mounting position | any |
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Specifications may be subject to change without notice