Product Model

FLKM-2KS40/PMT/YCS

In Stock
Last updated: 2025/4/25
Phoenix Contact FLKM-2KS40/PMT/YCS

Selling Points

  • 1Compatible with Yokogawa AAI, AAV, and AAB modules for seamless integration.
  • 2Meets overvoltage category II and pollution degree 2 standards for reliable performance.
  • 3Supports multiple conductor cross sections (rigid and flexible) for versatile use.
  • 4Compact dimensions (180.1 mm x 111.8 mm x 55.4 mm) for space-saving installations.
  • 5Operates within -20 °C to 70 °C ambient temperature range for diverse environments.
Product Details
FLKM-2KS40/PMT/YCS
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Interface module
No. of channels
8
Operating mode
100% operating factor
Article revision
03
Insulation
Functional insulation
Overvoltage category
II
Pollution degree
2
Operating voltage (AC)
≤ 50 V AC
Operating voltage (DC)
≤ 60 V DC
Current (per branch)
≤ 1 A
Rated insulation voltage
63 V
Rated surge voltage
0.6 kV (1.2/50 μs)
Suitable I/O card
AAI135 AAI835
Suitable I/O card
NFAI135 NFAI835
Connection method
Yokogawa KS-compatible
Number of connections
2
Number of positions
40
Tightening torque
0.5 Nm
Pitch
2.54 mm
Connection method
Screw connection with disconnect knife
Stripping length
8 mm
Screw thread
M3
Number of positions
24
Conductor cross section rigid
0.2 mm² ... 4 mm²
Conductor cross-section rigid (2 conductors with same cross section)
0.2 mm² ... 1 mm²
Conductor cross section flexible
0.2 mm² ... 4 mm² 0.25 mm² ... 1.5 mm² (Ferrule without plastic sleeve) 0.25 mm² ... 1.5 mm² (Ferrule with plastic sleeve)
Conductor cross section flexible (2 conductors with same cross section)
0.2 mm² ... 1 mm² 0.25 mm² ... 0.75 mm² (Ferrule without plastic sleeve) 0.5 mm² ... 1 mm² (TWIN ferrule with plastic sleeve)
Conductor cross section AWG
24 ... 12
Tightening torque
0.5 Nm ... 0.6 Nm
Pitch
5.08 mm
Status display present
No
Width
134.8 mm
Height
77 mm
Depth
57.1 mm
Degree of protection (Module)
IP00
Degree of protection (Installation location)
≤ IP54
Ambient temperature (operation)
-20 °C ... 50 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Altitude
≤ 2000 m
Certificate
UKCA-compliant
Standards/regulations
EN IEC 60664-1
Mounting type
DIN rail mounting
Mounting position
any
Notes on operation
For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.

Specifications may be subject to change without notice