Product Model

FLKM-2KS50/32DO/YCS/ZFKDS

In Stock
Last updated: 2025/4/19
Phoenix Contact FLKM-2KS50/32DO/YCS/ZFKDS

Selling Points

  • 1Ensures high reliability with dual voltage supply and 50-pos. system connection.
  • 2Ideal for Yokogawa ADV551 card applications with 32 channels.
  • 3Easy and secure connection method for field-level connections.
  • 4Supports up to 4 A total current across all branches.
  • 5Meets EN 50178 standards and has a rated insulation voltage of 50 V.
Product Details
FLKM-2KS50/32DO/YCS/ZFKDS
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Interface module
Operating mode
100% operating factor
Insulation
Functional insulation
Overvoltage category
II
Pollution degree
2
Max. permissible operating voltage
30 V DC
Max. permissible current
100 mA (per path)
Max. permissible total current
4 A (Protected by slow-blow fuse 4 A, 5x20 (short-circuit protection only))
Nominal voltage U
24 V DC
Max. total current of all branches
4 A
Rated insulation voltage
50 V
Rated surge voltage
0.5 kV
Suitable I/O card
ADV551
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.2 mm² ... 4 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Connection method
Yokogawa KS-compatible
Number of connections
2
Number of positions
50
Tightening torque
0.5 Nm
Status display present
Yes
Operating voltage display
Green LED
Width
180 mm
Height
90 mm
Depth
77 mm
Degree of protection
IP00
Degree of protection (Installation location)
≥ IP54 (Installation location)
Ambient temperature (operation)
-20 °C ... 50 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Altitude
≤ 2000 m
Standards/regulations
EN IEC 60664-1
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any
Notes on operation
No additional touch protection is required when using a SELV/PELV voltage (≤ 25 V AC or 60 V DC).
Notes on operation
At least one functional insulation against adjacent modules is complied with (in the support rail direction). If the application has stricter requirements for the insulation (basic insulation or reinforced insulation), they must be realized by applying suitable measures (e. g. partition plates).
Notes on operation
For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.

Specifications may be subject to change without notice