Product Model
FLKM-2KS50/32DO/YCS/ZFKDS

Selling Points
- 1Ensures high reliability with dual voltage supply and 50-pos. system connection.
- 2Ideal for Yokogawa ADV551 card applications with 32 channels.
- 3Easy and secure connection method for field-level connections.
- 4Supports up to 4 A total current across all branches.
- 5Meets EN 50178 standards and has a rated insulation voltage of 50 V.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Interface module | Operating mode | 100% operating factor |
Insulation | Functional insulation | Overvoltage category | II |
Pollution degree | 2 | Max. permissible operating voltage | 30 V DC |
Max. permissible current | 100 mA (per path) | Max. permissible total current | 4 A (Protected by slow-blow fuse 4 A, 5x20 (short-circuit protection only)) |
Nominal voltage U | 24 V DC | Max. total current of all branches | 4 A |
Rated insulation voltage | 50 V | Rated surge voltage | 0.5 kV |
Suitable I/O card | ADV551 | Connection method | Spring-cage connection |
Stripping length | 8 mm | Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | Conductor cross section AWG | 24 ... 12 |
Connection method | Yokogawa KS-compatible | Number of connections | 2 |
Number of positions | 50 | Tightening torque | 0.5 Nm |
Status display present | Yes | Operating voltage display | Green LED |
Width | 180 mm | Height | 90 mm |
Depth | 77 mm | Degree of protection | IP00 |
Degree of protection (Installation location) | ≥ IP54 (Installation location) | Ambient temperature (operation) | -20 °C ... 50 °C |
Ambient temperature (storage/transport) | -20 °C ... 70 °C | Altitude | ≤ 2000 m |
Standards/regulations | EN IEC 60664-1 | Mounting type | DIN rail mounting |
Assembly note | in rows with zero spacing | Mounting position | any |
Notes on operation | No additional touch protection is required when using a SELV/PELV voltage (≤ 25 V AC or 60 V DC). | Notes on operation | At least one functional insulation against adjacent modules is complied with (in the support rail direction). If the application has stricter requirements for the insulation (basic insulation or reinforced insulation), they must be realized by applying suitable measures (e. g. partition plates). |
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Specifications may be subject to change without notice