Product Model
FLKM 40/FFKDS/V/SO355

Selling Points
- No selling points available for this product.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Interface module | Product family | VARIOFACE |
Insulation | Functional insulation | Overvoltage category | II |
Pollution degree | 2 | Operating voltage (AC) | ≤ 30 V AC |
Operating voltage (DC) | ≤ 60 V DC | Current (per branch) | ≤ 1 A |
Rated insulation voltage | 63 V | Rated surge voltage | 0.6 kV (1.2/50 μs) |
Connection in acc. with standard | IEC 60603-13 | Connection method | IDC/FLK pin strip |
Number of connections | 1 | Number of positions | 40 |
Insertion/withdrawal cycles | > 50 | Connection method | Push-in spring connection |
Stripping length | 10 mm | Number of positions | 40 |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² | Conductor cross section flexible | 0.2 mm² ... 1.5 mm²
0.25 mm² ... 0.75 mm² (Ferrule without plastic sleeve)
0.25 mm² ... 0.75 mm² (Ferrule with plastic sleeve) |
Conductor cross section AWG | 24 ... 16 | Pitch | 5.08 mm |
Width | 112 mm | Height | 90 mm |
Depth | 61 mm | Degree of protection (Module) | IP00 |
Degree of protection (Installation location) | ≥ IP54 | Ambient temperature (operation) | -20 °C ... 50 °C |
Ambient temperature (storage/transport) | -20 °C ... 70 °C | Altitude | ≤ 2000 m |
Standards/regulations | EN IEC 60664-1 | Mounting type | DIN rail mounting |
Mounting position | any | Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Specifications may be subject to change without notice