Product Model

FLM BK PB M12 DI 8 M12-EF

In Stock
Last updated: 2025/4/22
Phoenix Contact FLM BK PB M12 DI 8 M12-EF

Selling Points

  • 1Supports up to 16 devices: Ideal for connecting multiple standard or PCP devices on a local bus.
  • 28 Digital Inputs: Includes 8 digital inputs for various applications, ensuring comprehensive data collection.
  • 3Dynamic Configuration: Allows for channel-specific diagnostics and dynamic configuration for flexible setup.
  • 4M12 Fast Connection Technology: Utilizes M12 connectors with SPEEDCON fast locking system for secure and efficient connections.
  • 5IP65/IP67 Protection: Offers robust protection against dust and water, ensuring reliable operation in harsh environments.
Product Details
FLM BK PB M12 DI 8 M12-EF
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
70 mm
Height
178 mm
Depth
50 mm
Drill hole spacing
168 mm
Color
anthracite
Connection method
M12 connector, B-coded
Designation connection point
Copper cable
Number of positions
5
Transmission speed
9.6 kbps ... 12 Mbps
Address area assignment
1 ... 126, adjustable
Designation
Local bus gateway
Connection method
M12 connector, B-coded
Transmission speed
500 kbaud/2 Mbaud, can be selected
Max. length of local bus
20 m
Max. number of local bus devices
16
Number of local bus devices that can be connected
max. 16
Number of devices with parameter channel
max. 16
Input address area
8 bit
Output address area
1 Byte
Register length
8 bit
Input name
Digital inputs
Description of the input
IEC 61131-2 type 1
Number of inputs
8 (double-occupancy)
Connection method
M12 connector
Connection technology
2-, 3-, 4-conductor
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
13 V DC ... 30 V DC
Nominal input voltage U
24 V DC
Filter time
3 ms
Protective circuit
Reverse polarity protection
Product type
I/O component
Product family
Fieldline
Type
modular
No. of channels
8
Voltage supply U
24 V DC
Power supply at U
max. 4 A
Current consumption from U
max. 100 mA (At 2 Mbaud) typ. 75 mA (At 2 Mbaud) max. 100 mA (At 500 kBaud) typ. 75 mA (At 500 kBaud)
Voltage supply U
24 V DC
Power supply at U
max. 4 A
Current consumption from U
typ. 15 mA (plus power supply for sensors) max. 600 mA
Connection method
M12 connector
Designation
U
Supply voltage
24 V DC
Supply voltage range
18 V DC ... 30 V DC (including ripple)
Test voltage: To I/O
500 V AC
Connection method
M12 connector
Ambient temperature (operation)
-25 °C ... 60 °C
Degree of protection
IP65/IP67
Air pressure (operation)
80 kPa ... 106 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (storage/transport)
95 %
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
Wall mounting, optionally on mounting panel Wall mounting

Specifications may be subject to change without notice