Product Model

FLS CO M12 DI 16 M12

In Stock
Last updated: 2025/4/19
Phoenix Contact FLS CO M12 DI 16 M12

Selling Points

  • 116 Digital Inputs: The device features 16 IEC 61131-2 type 1 digital inputs for efficient signal acquisition.
  • 2Fast M12 Connections: Utilizes SPEEDCON fast locking system and M12 connectors for consistent and reliable connections.
  • 3Comprehensive Protection: Equipped with short-circuit and overload protection, as well as reverse polarity protection.
  • 4Flexible Power Supply: Supports a flexible power supply concept, ensuring stable operation under various conditions.
  • 5Diagnostic Indicators: Includes diagnostic and status indicators for easy monitoring and troubleshooting.
Product Details
FLS CO M12 DI 16 M12
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
60 mm
Height
161 mm
Depth
44.5 mm
Drill hole spacing
151 mm
Connection method
2 M12 connectors, A-coded
Number of positions
5
Transmission speed
10, 20, 50, 125, 250, 500, 1000 kBit/s (Automatic baud rate detection)
Transmission physics
Copper cable with optional power supply in acc. with CAN standard
Address area assignment
1 ... 126, adjustable
Number of local bus devices that can be connected
0
Number of devices with parameter channel
0
Input address area
16 bit
Output address area
0 bit
Register length
16 bit
Input name
Digital inputs
Description of the input
IEC 61131-2 type 1
Number of inputs
16
Connection method
M12 connector, double occupancy
Connection technology
2-, 3-, 4-conductor
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
13 V DC ... 30 V DC
Nominal input voltage U
24 V DC
Filter time
1 ms
Protective circuit
Reverse polarity protection
Product type
I/O component
Product family
Fieldline
Type
Block design
No. of channels
16
Voltage supply U
24 V DC
Power supply at U
max. 4 A
Current consumption from U
typ. 65 mA max. 100 mA
Voltage supply U
24 V DC
Power supply at U
max. 4 A
Current consumption from U
typ. 8 mA (plus sensor current) max. 1.2 A
Connection method
M12 connector (A-coded)
Designation
U
Supply voltage
24 V DC
Supply voltage range
18 V DC ... 30 V DC (including ripple)
Test voltage: 24 V supply (bus logics) / Digital inputs (sensor supply / I/O)
500 V AC, 50 Hz, 1 min
Test voltage: FE / Digital inputs (sensor supply)
500 V AC, 50 Hz, 1 min
Connection method
M12 connector
Ambient temperature (operation)
-25 °C ... 60 °C
Degree of protection
IP65/IP67
Air pressure (operation)
80 kPa ... 106 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (storage/transport)
95 %
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
Wall mounting

Specifications may be subject to change without notice