Product Model
FLS IB M12 DI 8 M12

Selling Points
- 1High-Performance Connectivity: Features M12 connectors for secure and reliable connections in harsh industrial environments.
- 2Versatile Input/Output: Supports 2-, 3-, and 4-conductor connections, catering to various industrial control needs.
- 3Durable Design: Built with robust materials to withstand demanding industrial conditions.
- 4Easy Installation: Simple setup with standard M12 connectors, reducing installation time and effort.
- 524V DC Power Supply: Operates on a stable 24V DC power supply, ensuring consistent performance in industrial settings.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 60 mm | Height | 161 mm |
Depth | 44.5 mm | Drill hole spacing | 151 mm |
Connection method | 2x M12 connectors, B-coded | Designation connection point | Copper cable |
Number of positions | 5 | Transmission speed | 500 kbps |
Number of local bus devices that can be connected | 0 | Number of devices with parameter channel | 0 |
ID code (dec.) | 2 | ID code (hex) | 02 |
Length code (hex) | 81 | Length code (dec) | 129 |
Process data channel | 0 bit | Input address area | 8 bit |
Output address area | 0 bit | Register length | 8 bit |
Input name | Digital inputs | Description of the input | IEC 61131-2 type 1 |
Number of inputs | 8 | Connection method | M12 connector |
Connection technology | 2-, 3-, 4-conductor | Input voltage | 24 V DC |
Input voltage range "0" signal | -30 V DC ... 5 V DC | Input voltage range "1" signal | 13 V DC ... 30 V DC |
Nominal input voltage U | 24 V DC | Filter time | 3 ms |
Protective circuit | Reverse polarity protection | Product type | I/O component |
Product family | Fieldline | Type | Block design |
No. of channels | 8 | Voltage supply U | 24 V DC |
Power supply at U | max. 4 A | Current consumption from U | typ. 65 mA
max. 100 mA |
Voltage supply U | 24 V DC | Power supply at U | max. 4 A |
Current consumption from U | typ. 5 mA (plus sensor current)
max. 700 mA | Connection method | M12 connector (A-coded) |
Designation | U | Supply voltage | 24 V DC |
Supply voltage range | 18 V DC ... 30 V DC (including ripple) | Test voltage: 24 V supply (bus logics) / FE | 500 V AC, 50 Hz, 1 s |
Test voltage: 24 V supply (bus logics) / Digital inputs (sensor supply / I/O) | 500 V AC, 50 Hz, 1 s | Test voltage: 24 V supply (bus logics) / Incoming remote bus | 500 V AC, 50 Hz, 1 s |
Test voltage: 24 V supply (bus logics) / Outgoing remote bus | 500 V AC, 50 Hz, 1 s | Test voltage: Digital inputs (sensor supply / I/O) / FE | 500 V AC, 50 Hz, 1 s |
Test voltage: Digital inputs (sensor supply / I/O) / Incoming remote bus | 500 V AC, 50 Hz, 1 s | Test voltage: Digital inputs (sensor supply / I/O) / Outgoing remote bus | 500 V AC, 50 Hz, 1 s |
Test voltage: Incoming remote bus / FE | 500 V AC, 50 Hz, 1 s | Test voltage: Incoming remote bus / Outgoing remote bus | 500 V AC, 50 Hz, 1 s |
Test voltage: Outgoing remote bus / FE | 500 V AC, 50 Hz, 1 s | Connection method | M12 connector |
Ambient temperature (operation) | -25 °C ... 60 °C | Degree of protection | IP65/IP67 |
Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (storage/transport) | 95 % |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | Mounting type | Wall mounting |
Specifications may be subject to change without notice