Phoenix Contact FL SWITCH 2314-2SFP PN

Selling Points

  • 114 RJ45 Ports & 2 SFP Ports: Supports 10/100/1000 Mbps Ethernet and 100/1000 Mbps SFP connections.
  • 2PROFINET Conformance-Class B: Ensures compatibility with PROFINET networks for industrial automation.
  • 3Extended Temperature Range: Operates from -40°C to 70°C, making it suitable for harsh environments.
  • 4Advanced Network Features: Includes MRP, RSTP, VLANs, DHCP client/server, and IGMP Snooping for robust network management.
  • 5Easy Commissioning & Management: Utilizes FL NETWORK MANAGER software for fast and easy startup and configuration.
Product Details
FL SWITCH 2314-2SFP PN
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
85 mm
Height
130 mm
Depth
119 mm
General
Support by phone or on-site (fee is charged)
Note on application
Only for industrial use
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Housing material
Polycarbonate fiber reinforced
Mounting type
DIN rail mounting
Connection method
RJ45
Note on the connection method
Auto negotiation and autocrossing
Transmission speed
10/100/1000 Mbps
Transmission physics
Copper
Transmission length
100 m (per segment)
Signal LEDs
Data receive, link status
No. of channels
14 (RJ45 ports)
Number of interfaces
2
Connection method
SFP
Transmission speed
100/1000 Mbps (full duplex)
Transmission physics
Depending on the SFP module
Transmission length
up to 80 km (Depending on the fiber/SFP module used)
Signal LEDs
Data receive, link status
No. of channels
2 (SFP ports)
Output name
Alarm output
Product type
Switch
Product family
Managed Switch 2000
Type
Book type
MTTF
379.84 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) 199.41 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) 27.52 Years (SN 29500 standard, temperature 55°C, operating cycle 100%)
Special properties
Extended temperature range PROFINET mode preset, PROFINET status LEDs Development process certified in accordance with IEC 62443-4-1 Compatible with IEC 62443-4-2
Signal delay
≥ 1.9 µs (Store-and-Forward mode, 10/100/1000 Mbps, depending on the frame size)
Article revision
06
Protection class
III (VDE 0106)
Degree of pollution
2
Diagnostic functions
RMON History LLDP (Link Layer Discovery Protocol) SNMP-Traps N:1-Portmirroring ACD (Address Conflict Detection) SysLog CRC-Surveillance
Basic functions
Store-and-forward switch, complies with IEEE 802.3
Signal contact control voltage
typ. 24 V DC
PROFINET conformance class
Conformance-Class B
PROFINET device function
PROFINET device Fast Startup
Filter functions
Quality of Service (8 priority classes) Class of Service DiffServ/DSCP Port-Priorisierung VLAN (up to 32 VLANs) IGMP Snooping/Querier (v1/v2) Auto-Query-Port Extended Multicast Filtering
IP parameterization
DHCP client DHCP Option 82 (Relay Agent) DHCP server (pool-based, port-based) BootP DCP (Discovery and Configuration Protocol)
MAC address table
8k
Management
Web-based management (HTTP/HTTPS) Role-based user management (LDAP, RADIUS) SNMPv1/v2/v3 Command Line Interface (Telnet, SSH)
Redundancy
MRP (Media Redundancy Protocol) RSTP (Rapid Spanning Tree Protocol) FRD (Fast Ring Detection) Large Tree Support LACP (Link Aggregation Control Protocol) PROFINET S2 system redundancy
Status and diagnostic indicators
LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (link/activity and speed), PROFINET status LEDs (BF, SF)
Additional functions
Jumbo frames (max. 9,600 bytes) Transmission of MMS and GOOSE (IEC 61850-8-1) Transmission of Modbus/TCP
Time synchronization
SNTP (Simple Network Time Protocol)
Port security
MAC-based, RADIUS (IEEE 802.1X), MAC Authentication Bypass
Basic functions
Store-and-forward switch, complies with IEEE 802.3
Current consumption
325 mA
Local diagnostics
US1/2 Supply voltage US1, US2 Green LED FAIL Div. LED red LINK Link status Green LED BF Bus errors LED red SF Group error LED red
Maximum power dissipation for nominal condition
15.6 W (U
Test section
24 V supply / functional ground 500 V DC 1 min Ethernet interface/all other potentials 2.25 kV DC 1 min
Transmission medium
Copper FO
Supply voltage (DC)
24 V DC (redundant)
Supply voltage range
12 V DC ... 57 V DC
Power supply connection
via COMBICON, max. conductor cross section 1.5 mm²
Residual ripple
3.6 V
Max. current consumption
2 A (U
Typical current consumption
460 mA (at U
Current consumption
325 mA
Signal contact control voltage
typ. 24 V DC
Connection method
Push-in spring connection
Note on the connection method
Use only copper connecting cables providing the permitted temperature range (-40 °C ... 75 °C).
Conductor cross section, rigid
0.25 mm² ... 1.5 mm²
Conductor cross section, flexible
0.25 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Stripping length
9 mm
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Shock (operation)
30g (EN 60068-2-27)
Vibration (operation)
in acc. with IEC 60068-2-6: 5g, 150 Hz
Air pressure (operation)
80 kPa ... 110 kPa up to 2000 m above mean sea level (Without derating)
Air pressure (storage/transport)
79 kPa ... 108 kPa up to 2000 m above mean sea level (Without derating)
Free from substances that could impair the application of coating
Yes
Shipbuilding approval
Tested in accordance with IEC 60945 and IACS E10
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
DEMKO 16 ATEX 1709X
References to standards
EN 60079-0 EN 60079-7
Identification
Ex ec IIC T4 Gc
Certificate
IECEx ULD 16.0018 X
References to standards
IEC 60079-0 IEC 60079-7
Identification
cULus
Identification
Class I, Division 2, Groups A, B, C, and D, T4 Class I, Zone 2, AEx ec IIC T4 Ex ec IIC T4 Gc X
Certificate
E366272
Note
UL 60079-0 Ed. 6 / UL 60079-7 Ed. 5, CSA 22.2 No. 60079-0 Ed. 3 / CSA C22.2 No. 60079-7 Ed. 2
Identification
2Ex e IIC T4 Gc X
Certificate
RU C-DE.HB49.B.00118/21
Identification
Install the device in a suitable, approved housing with at least IP66 protection. The housing/control cabinet must be equipped with a warning sign prohibiting opening in the potentially explosive area. The operation of devices is permitted if all optical ports are connected or sealed with the supplied filler plugs.
Identification
Ex ec IIC T4 Gc
Certificate
2022122310115629
Identification
ISA S71.04.2013 G3 Harsh Group A
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
PxCIMA22UKEX2702910X
Temperature
B
Humidity
B
Vibration
A
EMC
B
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Conformance with EMC directives
EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion A EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A EN 61000-6-2 EN 61000-4-5 (surge) Criterion A EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A EN 61000-6-2 EN 61000-6-3 (noise emission) Class B EN 61000-6-2 EN 61000-6-3 (conducted emissions) Class B
Noise immunity
EN 61000-6-2
Noise emission
EN 61000-6-4
Basic functions
Store-and-forward switch, complies with IEEE 802.3
Status display
LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (link/activity and speed), PROFINET status LEDs (BF, SF)

Specifications may be subject to change without notice