Product Model

FL SWITCH APL 2224-4A-213-PA

In Stock
Last updated: 2025/4/19
Phoenix Contact FL SWITCH APL 2224-4A-213-PA

Selling Points

  • 1Direct Two-Wire Ethernet Connection: The FL SWITCH APL 2224-4A-213-PA enables direct two-wire Ethernet connection of sensors and field devices in Ex zones.
  • 2Zone 2 Mountable and Ex ‘ia’ APL Ports: Designed for use in potentially explosive areas, meeting high safety standards for zone 1 and 2 applications.
  • 324-Port Ethernet-APL + PROFIBUS PA: Integrates 24 APL ports with four uplink ports, supporting both Ethernet-APL and PROFIBUS PA protocols.
  • 4High Reliability and Redundancy: Features real-time QoS, redundancy, and security features for efficient and secure data transmission.
  • 5Wide Range and Flexibility: Supports trunk and spur topology for long ranges up to 1,000 m at 10 Mbps, with flexible network design options.
Product Details
FL SWITCH APL 2224-4A-213-PA
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
270 mm
Height
215 mm
Depth
127 mm
Note on dimensions
Depth valid when a TH 35-15 DIN rail is used (according to EN 60715).
Note on application
Only for industrial use
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Housing material
Die-cast aluminum Polycarbonate
Number of interfaces
2
Connection method
RJ45
Note on the connection method
Auto negotiation and autocrossing
Transmission speed
10/100 Mbps
Transmission physics
Copper
Transmission length
100 m (per segment)
Signal LEDs
Data receive, link status
No. of channels
2 (RJ45 ports)
Number of interfaces
2
Connection method
SFP
Note on the connection method
Full duplex
Transmission speed
100/1000 Mbps (full duplex)
Transmission physics
FO
Transmission length
Depending on the SFP module used
No. of channels
2 (SFP ports)
Connection method
Screw connection
Note on the connection method
APL, full duplex
Transmission speed
10 Mbps
Transmission physics
Copper
No. of channels
24 (APL ports)
Power Class
SPAA
Note
Each port configurable via software
Output nominal voltage
≥ 9.6 V DC
Output current
≥ 55.56 mA
Output power
≥ 0.54 W
Power Class
SPBA
Note
Each port configurable via software
Output nominal voltage
≥ 8.9 V DC
Output current
≤ 100 mA
Output power
≤ 0.89 W
Power Class
SPBA
Note
Each port configurable via software
Output nominal voltage
≥ 8.9 V DC
Output current
≥ 93 mA
Output power
≤ 0.83 W
Product type
Switch
Product family
Managed Switch 2000
MTTF
37.59 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) 19.62 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) 11.6 Years (SN 29500 standard, temperature 70°C, operating cycle 100%)
Special properties
PROFIBUS PA field switch Zone 2 mountable Ex ‘ia’ APL ports four uplink ports
Article revision
02
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Overvoltage category
II
Degree of pollution
2
Diagnostic functions
RMON History LLDP (Link Layer Discovery Protocol) SNMP-Traps N:1-Portmirroring ACD (Address Conflict Detection) SysLog CRC-Surveillance
Filter functions
Quality of Service (8 priority classes) Class of Service DiffServ/DSCP Port prioritization VLAN (up to 32 VLANs) IGMP Snooping/Querier (v1/v2) Auto-Query-Port Extended Multicast Filtering
IP parameterization
DHCP client DHCP Option 82 (Relay Agent) DHCP server (pool-based, port-based) BootP DCP (Discovery and Configuration Protocol)
MAC address table
8k
Management
Web-based management (HTTP/HTTPS) Role-based user management (LDAP, RADIUS) SNMPv1/v2/v3
Redundancy
MRP (Media Redundancy Protocol) RSTP (Rapid Spanning Tree Protocol) Large Tree Support LACP (Link Aggregation Control Protocol) PROFINET S2 system redundancy
Time synchronization
SNTP (Simple Network Time Protocol)
Current consumption
5.75 A
Power consumption
25 W (No-load)
Maximum power dissipation for nominal condition
50 W (24 Class A ports at max. load (22 V DC supply voltage at 70°C))
Test section
Supply Voltage/spurs 1500 V ACrms 100BASE-T / Spurs 1500 V ACrms SFP / Spurs 1500 V ACrms Spurs / Earth Ground (Housing) 500 V ACrms Block of Spurs / Block of Spurs 500 V ACrms Supply / 100BASE-T 2000 V ACrms 100BASE-T / 100BASE-T 2000 V ACrms Supply / SFP 1500 V ACrms
Supply voltage (DC)
24 V DC (Redundancy)
Supply voltage range
22 V DC ... 30 V DC (Redundancy)
Max. current consumption
5.75 A
Current consumption
5.75 A
Connection method
Pluggable screw connection
Conductor cross section, rigid
0.2 mm² ... 2.5 mm²
Conductor cross section, flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Stripping length
7 mm
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C (horizontal) -40 °C ... 60 °C (vertical)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
2000 m (maximum)
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
5 % ... 95 % (non-condensing)
Shock (operation)
15g (IEC 600868-2-27)
Vibration (operation)
1g, according to EN 60068-2-6
Identification
 II 3(1) G Ex ic ec [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIIC
Certificate
UL 23 ATEX 2992X
Identification
Ex ic ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC
Certificate
IECEx UL 23.0028X
Identification
 II 3(1) G Ex ic ec [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIIC
Certificate
UL23UKEX2830X
Identification
Ind. Cont. Eq. E238705 also Listed Ind. Cont. Eq. for haz. loc. E196811 Install in: Class I, Div. 2, Groups A, B, C, D T4 Intrinsically safe outputs for: Class I, Div. 2, Groups A, B, C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz. Loc. Class I, Zone 2, AEx ic ec [ia Ga] IIC T4 Gc, [AEx ia Da] IIIC Ex ic ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC
Identification
Ex ic ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC
Max. output voltage U
13.23 V
Max. output current I
279.38 mA
Max. output power P
1.66 W
Safety-related maximum voltage U
60 V
A, B / IIC: Max. external inductivity L
/ 0.5 µF
C/IIB, IIIC: Max. external inductivity L
/ 1.3 µF
D/IIA, E, F, G, Class III: Max. external inductivity L
/ 1.4 µF
A, B / IIC: Max. external inductivity L
0.15 mH
C/IIB, IIIC: Max. external inductivity L
1.5 mH
D/IIA, E, F, G, Class III: Max. external inductivity L
2.6 mH
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU (Test requirements for NE 21, IEC 61326-7 also considered as per the APL EMC specifications)
Conformance with EMC directives
EN 61000-6-2 EN 61000-4-2 (ESD) Criterion A, ±6 kV contact discharge, ±8 kV air discharge EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion A, Field intensity: 10 V/m EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A, supply lines: ±2 kV, signal/data lines: ±1 kV EN 61000-6-2 EN 61000-4-5 (surge) Criterion A, ±1 kV supply line L-PE; ±1 kV supply line N-PE; ±1 kV shielded I/O signal lines for metallic enclosure devices EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A, 10 Vrms EN 61000-6-2 IEC 61000-4-16 (common mode disturbances) Criterion A: 10V (10 kHz to 150 kHz) EN 61000-6-4 EN 55011 (emitted interference) Class A
Noise immunity
EN 61000-6-2
Noise emission
EN 61000-6-4

Specifications may be subject to change without notice