Product Model

FLT 35 CTRL-1.5/I

In Stock
Last updated: 2025/4/20
Phoenix Contact FLT 35 CTRL-1.5/I

Selling Points

  • 1High Discharge Capacity: Handles up to 50 kA of discharge current.
  • 2Protection Level: Offers 1.5 kV protection level for reliable voltage protection.
  • 3Compact Design: Measures 35 mm in width, ideal for DIN rail mounting.
  • 4Fast Response Time: Responds in less than 100 ns to lightning surges.
  • 5Comprehensive Standards Compliance: Meets IEC 61643-1, UL 1449, and other international standards.
Product Details
FLT 35 CTRL-1.5/I
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Combination type
IEC test classification
I T1
EN type
T1
Type
DIN rail module, one-piece 
Surge protection fault message
optical
Nominal frequency f
50 Hz 60 Hz
Nominal voltage U
230 V AC
Connection method
Screw connection
Screw thread
M5
Tightening torque, min
4.5 Nm
Stripping length
14.5 mm
Conductor cross section flexible min.
0.5 mm²
Conductor cross section flexible max.
25 mm²
Conductor cross section, rigid min.
0.5 mm²
Conductor cross section, rigid max.
35 mm²
Width
17.6 mm
Height
88.6 mm
Depth
66.2 mm
Horizontal pitch
1 Div.
Flammability rating according to UL 94
V0
Housing material
PA
Open side panel
No
Direction of action
1L-N/PE
Nominal frequency f
50 Hz 60 Hz
Maximum continuous voltage U
260 V AC
Maximum continuous operating voltage U
260 V AC
Maximum continuous operating voltage U
260 V AC
Residual current I
≤ 2.5 mA
Operating effective current I
≤ 2.5 mA
Nominal discharge current I
35 kA
Nominal discharge current I
35 kA
Nominal discharge current I
35 kA
Follow current quenching capacity I
3 kA (260 V)
Follow current quenching capacity I
3 kA (260 V)
Voltage protection level U
≤ 1.5 kV
Voltage protection level U
≤ 1.5 kV
Voltage protection level U
≤ 1.5 kV
Response time t
≤ 100 ns
Response time t
≤ 100 ns
Response time t
≤ 100 ns
Max. backup fuse with branch wiring
125 A (gL)
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 85 °C
Permissible humidity (operation)
≤ 95 %
Standards/regulations
IEC 60664-1 / VDE 0110-1
Standards/regulations
IEC 61643-1 E DIN VDE 0675-6 E DIN VDE 0675-6/A1 E DIN VDE 0675-6/A2 IEC 61312-1
Standards/specifications
IEC 61643-1
Note
1998-02
Standards/specifications
E DIN VDE 0675-6
Note
1989-11
Standards/specifications
E DIN VDE 0675-6/A1
Note
1996-03
Standards/specifications
E DIN VDE 0675-6/A2
Note
1996-10
Standards/specifications
IEC 61312-1
Note
1995-02
Mounting type
DIN rail: 35 mm

Specifications may be subject to change without notice