Product Model

FLT-CP-PLUS-350-ST

In Stock
Last updated: 2025/4/18
Phoenix Contact FLT-CP-PLUS-350-ST

Selling Points

  • 125 kA nominal discharge current for effective surge protection.
  • 2Built to withstand 25g shock and 5g vibration, ensuring durability in various environments.
  • 3Meets IP20 standards when all terminal points are used, providing reliable protection against solid objects.
  • 4Operates between -40°C to 80°C ambient temperature and up to 2000 meters altitude.
  • 5Plug-in/screw connection via COMBICON for quick and secure installation.
Product Details
FLT-CP-PLUS-350-ST
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Replacement plug
IEC test classification
I / II T1 / T2
EN type
T1 / T2
IEC power supply system
TN TT
Type
Male
Number of positions
1
Surge protection fault message
optical
Overvoltage category
III
Pollution degree
2
Nominal frequency f
50 Hz (60 Hz)
Connection method
pluggable
Width
35.45 mm
Height
46.6 mm
Depth
56.4 mm
Horizontal pitch
2 Div.
Color
blue grey (RAL 7031)
Flammability rating according to UL 94
V-0
CTI value of material
600
Insulating material
PA 6.6/PBT
Material group
I
Housing material
PBT
Mode of protection
L-N L-PEN
Direction of action
L-N / L-PEN
Nominal voltage U
240 V AC (TN) 240 V AC (TT)
Nominal frequency f
50 Hz (60 Hz)
Maximum continuous voltage U
350 V AC
Nominal discharge current I
25 kA
Maximum discharge current I
50 kA
Impulse discharge current (10/350) µs, charge
12.5 As
Impulse discharge current (10/350) µs, specific energy
160 kJ/Ω
Impulse discharge current (10/350) µs, peak value l
25 kA
Follow current interrupt rating I
50 kA
Short-circuit current rating I
50 kA
Voltage protection level U
≤ 1.5 kV
Residual voltage U
≤ 1.5 kV (at I
Front of wave sparkover voltage at 6 kV (1.2/50) µs
≤ 1.5 kV
TOV behavior at U
415 V AC (5 s / withstand mode) 457 V AC (120 min / withstand mode)
Response time t
≤ 100 ns
Max. backup fuse with branch wiring
315 A (gG)
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl)
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (5 - 500 Hz/2.5 h/X, Y, Z)
Maximum continuous operating voltage MCOV (L-N)
264 V AC
Nominal discharge current I
20 kA
Mode of protection
L-N
Nominal voltage
240 V AC
Power distribution system
Split phase
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
1350 V
Follow current (L-N)
10 kA (264 V AC)
SPD Type
4CA
Standards/regulations
EN 60664-1 / IEC 60664-1 / IEC 61643-11
Standards/specifications
IEC 61643-11
Note
2011
Standards/specifications
EN 61643-11
Note
2012
Mounting type
on base element

Specifications may be subject to change without notice