Product Model

FLT-PLUS CTRL-1.5/I

In Stock
Last updated: 2025/4/19
Phoenix Contact FLT-PLUS CTRL-1.5/I

Selling Points

  • 1Offers protection up to 1.5 kV against lightning and surge currents.
  • 2Measuring 35.5 mm in width, 150 mm in height, and 80.5 mm in depth, ideal for DIN rail mounting.
  • 3Utilizes spark gap insulation and POM for enhanced electrical safety.
  • 4Handles nominal discharge surge currents of 50 kA, ensuring reliable operation under heavy loads.
  • 5Suitable for various environments, including industrial settings with ambient temperatures ranging from -40°C to 85°C.
Product Details
FLT-PLUS CTRL-1.5/I
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Combination type
IEC test classification
I T1
EN type
T1
Type
DIN rail module, one-piece 
Number of positions
1
Surge protection fault message
optical
Overvoltage category
III
Pollution degree
2
Nominal frequency f
50 Hz 60 Hz
Nominal voltage U
400 V AC
Connection method
Screw connection
Screw thread
M6
Tightening torque, min
8 Nm
Stripping length
19 mm
Conductor cross section flexible min.
16 mm²
Conductor cross section flexible max.
35 mm²
Conductor cross section, rigid min.
10 mm²
Conductor cross section, rigid max.
50 mm²
Width
35.5 mm
Height
149.8 mm
Depth
80.5 mm
Horizontal pitch
2 Div.
Flammability rating according to UL 94
V0
Spark gap insulation
PA 6.6 GF POM
Housing material
PBT/PA-F
Open side panel
No
Direction of action
1L-N/PE
Nominal frequency f
50 Hz 60 Hz
Maximum continuous voltage U
440 V AC
Maximum continuous operating voltage U
440 V AC
Maximum continuous operating voltage U
440 V AC
Residual current I
≤ 3 mA
Operating effective current I
≤ 3 mA
Nominal discharge current I
50 kA
Nominal discharge current I
50 kA
Nominal discharge current I
50 kA
Maximum discharge current I
50 kA
Impulse discharge current (10/350) µs, charge
25 As
Impulse discharge current (10/350) µs, specific energy
625 kJ/Ω
Impulse discharge current (10/350) µs, peak value l
50 kA
Follow current quenching capacity I
50 kA (at 400 V AC)
Follow current quenching capacity I
50 kA (at 400 V AC)
Voltage protection level U
≤ 1.5 kV
Voltage protection level U
≤ 1.5 kV
Voltage protection level U
≤ 1.5 kV
Response time t
≤ 100 ns
Response time t
≤ 100 ns
Response time t
≤ 100 ns
Max. backup fuse with branch wiring
250 A (gL)
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 85 °C
Permissible humidity (operation)
≤ 95 %
Standards/regulations
DIN VDE 0110-1 / IEC 60664-1 / DIN VDE 0675-6 / IEC 61643-1 / NF C61-740
Standards/regulations
E DIN VDE 0675-6/A1 UL 1449 IEEE C62.1 IEEE C62.41 IEC 61643-1 prEN 61643-1
Standards/specifications
IEC 61643-1
Note
1998
Standards/specifications
UL 1449
Note
ed. 2
Mounting type
DIN rail: 35 mm

Specifications may be subject to change without notice