Product Model
FLT-PLUS CTRL-2.5/I

Selling Points
- 1High-Voltage Protection: Offers 2.5 kV protection against lightning currents.
- 2Compact Design: Measures 35.5 mm in width, 150 mm in height, and 80.5 mm in depth.
- 3CE Compliant: Meets CE standards for export outside the EU and EEA.
- 4Robust Construction: Features a durable housing with a horizontal pitch of 2 Div.
- 5Reliable Performance: Equipped with arc chopping spark gap and ignition electronics for reliable operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Combination type | IEC test classification | I
T1 |
EN type | T1 | Type | DIN rail module, one-piece |
Number of positions | 1 | Surge protection fault message | optical |
Nominal frequency f | 50 Hz
60 Hz | Nominal voltage U | 400 V AC |
Connection method | Screw connection | Screw thread | M6 |
Tightening torque, min | 8 Nm | Stripping length | 19 mm |
Conductor cross section flexible min. | 16 mm² | Conductor cross section flexible max. | 35 mm² |
Conductor cross section, rigid min. | 10 mm² | Conductor cross section, rigid max. | 50 mm² |
Width | 35.5 mm | Height | 149.8 mm |
Depth | 80.5 mm | Horizontal pitch | 2 Div. |
Flammability rating according to UL 94 | V0 | Housing material | PBT/PA-F |
Open side panel | No | Direction of action | 1L-N/PE |
Nominal frequency f | 50 Hz
60 Hz | Maximum continuous voltage U | 440 V AC |
Maximum continuous operating voltage U | 440 V AC | Maximum continuous operating voltage U | 440 V AC |
Residual current I | ≤ 3 mA | Operating effective current I | ≤ 3 mA |
Nominal discharge current I | 50 kA | Nominal discharge current I | 50 kA |
Nominal discharge current I | 50 kA | Impulse discharge current (10/350) µs, charge | 25 As |
Impulse discharge current (10/350) µs, specific energy | 625 kJ/Ω | Impulse discharge current (10/350) µs, peak value l | 50 kA |
Follow current quenching capacity I | 50 kA (at 400 V AC) | Follow current quenching capacity I | 50 kA (at 400 V AC) |
Voltage protection level U | ≤ 2.5 kV | Voltage protection level U | ≤ 2.5 kV |
Voltage protection level U | ≤ 2.5 kV | Response time t | ≤ 100 ns |
Response time t | ≤ 100 ns | Response time t | ≤ 100 ns |
Max. backup fuse with branch wiring | 250 A (gL) | Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 85 °C | Permissible humidity (operation) | ≤ 95 % |
Standards/regulations | VDE 0110-1 / IEC 60664-1 / VDE 0675-6 / NF C61-740 | Standards/regulations | E DIN VDE 0675-6/A1
UL 1449
IEEE C62.1
IEEE C62.41
IEC 61643-1
prEN 61643-1 |
Standards/specifications | E DIN VDE 0675-6/A1 | Note | 1996 |
Standards/specifications | UL 1449 | Note | ed. 2 |
Standards/specifications | IEC 61643-1 | Note | 1998 |
Mounting type | DIN rail: 35 mm |
Specifications may be subject to change without notice