Product Model

IB IL 24 DI16-2MBD

In Stock
Last updated: 2025/4/23
Phoenix Contact IB IL 24 DI16-2MBD

Selling Points

  • 116 digital inputs for comprehensive signal acquisition.
  • 2Connection of sensors in 2- and 3-conductor technology.
  • 3Maximum permissible load current per sensor: 250 mA.
  • 4Diagnostic and status indicators for real-time monitoring.
  • 5IP20 protection for safe operation in various environments.
Product Details
IB IL 24 DI16-2MBD
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
140.5 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
EMC note
EMC: class A product, see manufacturer's declaration in the download area
No. of channels
2
Connection method
Inline data jumper
Transmission speed
2 Mbps
ID code (dec.)
190
ID code (hex)
BE
Length code (hex)
01
Length code (dec)
01
Process data channel
16 bit
Input address area
2 Byte
Output address area
0 Byte
Register length
16 bit
Required parameter data
1 Byte
Required configuration data
4 Byte
Input name
Digital inputs
Description of the input
EN 61131-2 type 1
Number of inputs
16
Connection method
Spring-cage connection
Connection technology
3-conductor
Input voltage
24 V DC (via voltage jumper)
Input voltage range "0" signal
-3 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Nominal input voltage U
24 V DC
Nominal input current at U
min. 3 mA (at nominal voltage)
Typical response time
< 1 ms
Protective circuit
Short-circuit and overload protection
Product type
I/O component
Product family
Inline
Type
modular Inline
Scope of delivery
without accessories
No. of channels
16
Operating mode
Process data mode with one word
Maximum power dissipation for nominal condition
14.5 W
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 80 mA
Power consumption
max. 0.6 W (at U
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 4 A
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice