Product Model

IB IL 24 DI 16-NPN

In Stock
Last updated: 2025/4/23
Phoenix Contact IB IL 24 DI 16-NPN

Selling Points

  • 116 NPN Digital Inputs: The terminal includes 16 NPN-wired digital inputs for precise signal acquisition.
  • 224 V DC Operation: Designed to operate at 24 V DC, ensuring reliable performance in various industrial settings.
  • 3Robust IP20 Protection: Equipped with IP20 protection, providing a high degree of protection against solid objects and dust.
  • 4500 kbps Transmission Speed: Supports a transmission speed of 500 kbps on the local bus, enhancing data transfer efficiency.
  • 5Diagnostic and Status Indicators: Includes diagnostic and status indicators for easy monitoring and troubleshooting.
Product Details
IB IL 24 DI 16-NPN
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Connection method
Inline data jumper
Transmission speed
500 kbps
ID code (dec.)
190
ID code (hex)
BE
Length code (hex)
01
Length code (dec)
01
Process data channel
16 bit
Input address area
2 Byte
Output address area
0 Byte
Register length
16 bit
Required parameter data
1 Byte
Input name
Digital inputs
Description of the input
EN 61131-2 type 1
Number of inputs
16
Connection method
Spring-cage connection
Connection technology
2-, 3-conductor
Input voltage
24 V DC (via voltage jumper)
Input voltage range "0" signal
-3 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Typical response time
< 1 ms
Protective circuit
Short-circuit and overload protection
Product type
I/O component
Product family
Inline
Type
modular
No. of channels
16
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 60 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 4 A
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice