Selling Points

  • 18 Digital Inputs: Connect up to 8 sensors with 24 V DC supply.
  • 2Robust Design: IP20 protection ensures reliable operation in various environments.
  • 3Spring-Cage Connection: Easy and secure connection method for digital inputs.
  • 4High-Speed Transmission: Supports transmission speeds of up to 500 kbps.
  • 5Diagnostic Indicators: Monitor status and diagnose issues with integrated diagnostic indicators.
Product Details
IB IL 24 DI 8-2MBD-PAC/SN
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Type
modular Inline
Scope of delivery
including Inline connectors and marking fields, connectors numbered individually
No. of channels
8
ID code (dec.)
190
ID code (hex)
BE
Length code (hex)
81
Length code (dec)
129
Process data channel
8 bit
Input address area
1 Byte
Output address area
0 Byte
Register length
8 bit
Required parameter data
1 Byte
Required configuration data
4 Byte
Supply voltage
7.5 V DC
Current draw
max. 50 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 2 A
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Input name
Digital inputs
Description of the input
EN 61131-2 type 1
Number of inputs
8 8
Connection method
Spring-cage connection
Connection technology
3-conductor
Input voltage
24 V DC
Input voltage range "0" signal
-3 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Typical response time
< 1 ms
Protective circuit
Short-circuit and overload protection
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
Inline data jumper
Transmission speed
2 Mbps
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting