Product Model

IB IL 24 DO 32/HD

In Stock
Last updated: 2025/4/18
Phoenix Contact IB IL 24 DO 32/HD

Selling Points

  • 1High-Performance Digital Outputs: The IB IL 24 DO 32/HD features 32 digital outputs with a nominal voltage of 24 V DC and a current of 500 mA per output.
  • 2Industrial-Grade Design: Built for industrial use, this terminal ensures reliability and durability in harsh environments.
  • 3Compact and Efficient: Measuring 48.8 mm in width, 119.8 mm in height, and 71.5 mm in depth, it fits seamlessly into DIN rail mounting systems.
  • 4Short-Circuit and Overload Protection: Equipped with short-circuit and overload protection, ensuring safe operation and extending the lifespan of the terminal.
  • 5Fast Transmission Speed: Supports a transmission speed of 500 kbps via the inline local bus, facilitating efficient data transfer and processing.
Product Details
IB IL 24 DO 32/HD
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Type
modular
No. of channels
32
Diagnostics messages
Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
ID code (dec.)
189
ID code (hex)
BD
Length code (hex)
02
Length code (dec)
02
Process data channel
32 bit
Input address area
0 Byte
Output address area
4 Byte
Register length
32 bit
Required parameter data
6 Byte
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 140 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 8 A
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Output name
Digital outputs
Connection method
Spring-cage connection
Connection technology
1-conductor
Number of outputs
32
Protective circuit
Overload protection, short-circuit protection of outputs
Output voltage
24 V (U
Maximum output current per channel
500 mA
Maximum output current per module
8 A
Nominal output voltage
24 V DC (voltage difference at I
Nominal load, inductive
12 VA
Nominal load, lamp
12 W
Nominal load, ohmic
12 W
Behavior with overload
Auto restart
Behavior with inductive overload
Output can be destroyed
Behavior at voltage switch-off
The output follows the power supply without delay
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
Inline data jumper
Diagnostics
Short-circuit or overload of the digital outputs
Message
Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Color
green
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice