Product Model
IB IL 24 DO 32/HD-2MBD-PAC

Selling Points
- 1The IB IL 24 DO 32/HD-PAC offers 32 digital outputs for efficient signal transmission.
- 2Designed with a robust construction and short-circuit/overload protection for reliable operation.
- 3Supports 1-conductor technology with spring-cage connections for secure and stable connections.
- 4Ideal for Inline stations with dimensions of 48.8 mm x 119.8 mm x 71.5 mm, ensuring a compact form factor.
- 5Meets IP20 protection standards and operates within a wide ambient temperature range (-25°C to 55°C).
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 48.8 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on dimensions | Housing dimensions |
Note on application | Only for industrial use | Number of interfaces | 2 |
Connection method | Inline data jumper | Transmission speed | 2 Mbps |
ID code (dec.) | 189 | ID code (hex) | BD |
Length code (hex) | 02 | Length code (dec) | 02 |
Process data channel | 32 bit | Input address area | 0 Byte |
Output address area | 4 Byte | Register length | 32 bit |
Required parameter data | 6 Byte | Required configuration data | 4 Byte |
Output name | Digital outputs | Connection method | Spring-cage connection |
Connection technology | 1-conductor | Number of outputs | 32 |
Protective circuit | Overload protection, short-circuit protection of outputs; electronic | Output voltage | 24 V (U |
Limitation of the voltage induced on circuit interruption | -45.8 V ... -15 V | Maximum inrush current | max. 1.5 A (at nominal lamp load for 20 ms) |
Output current | max. 500 mA (per channel)
max. 8 A (Device) | Nominal output voltage | 24 V DC |
Output voltage when switched off | max. 2 V | Output current when switched off | max. 300 µA |
Nominal load, inductive | 12 VA (1.2 H, 48 Ω) | Nominal load, lamp | 12 W |
Nominal load, ohmic | 12 W (48 Ω) | Maximum operating frequency with ohmic nominal load | max. 300 Hz (this switching frequency is limited by the data rate selected, the number of bus devices, the structure of the bus, the software used and the control or computer system used) |
Reverse voltage resistance to short pulses | Reverse voltage proof | Behavior with overload | Auto restart |
Behavior with inductive overload | Output can be destroyed | Behavior at voltage switch-off | The output follows the power supply without delay |
Overcurrent shut-down | min. 0.7 A | Output current with ground connection interrupt when switched off | max. 25 mA |
Product type | I/O component | Product family | Inline |
Type | modular | Scope of delivery | including Inline connectors and marking fields |
No. of channels | 32 | Operating mode | Process data operation with 2 words |
Diagnostics messages | Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module | Article revision | 09 |
Overvoltage category | II (IEC 60664-1, EN 60664-1) | Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Maximum power dissipation for nominal condition | 2.3 W | Supply voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 140 mA (HW 00)
max. 30 mA (from HW 01) | Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 8 A |
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min | Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min | Connection name | Inline connector |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Ambient temperature (operation) | -25 °C ... 55 °C | Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice