Product Model

IB IL 24 DO 32/HD-2MBD-PAC

In Stock
Last updated: 2025/4/17
Phoenix Contact IB IL 24 DO 32/HD-2MBD-PAC

Selling Points

  • 1The IB IL 24 DO 32/HD-PAC offers 32 digital outputs for efficient signal transmission.
  • 2Designed with a robust construction and short-circuit/overload protection for reliable operation.
  • 3Supports 1-conductor technology with spring-cage connections for secure and stable connections.
  • 4Ideal for Inline stations with dimensions of 48.8 mm x 119.8 mm x 71.5 mm, ensuring a compact form factor.
  • 5Meets IP20 protection standards and operates within a wide ambient temperature range (-25°C to 55°C).
Product Details
IB IL 24 DO 32/HD-2MBD-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Note on application
Only for industrial use
Number of interfaces
2
Connection method
Inline data jumper
Transmission speed
2 Mbps
ID code (dec.)
189
ID code (hex)
BD
Length code (hex)
02
Length code (dec)
02
Process data channel
32 bit
Input address area
0 Byte
Output address area
4 Byte
Register length
32 bit
Required parameter data
6 Byte
Required configuration data
4 Byte
Output name
Digital outputs
Connection method
Spring-cage connection
Connection technology
1-conductor
Number of outputs
32
Protective circuit
Overload protection, short-circuit protection of outputs; electronic
Output voltage
24 V (U
Limitation of the voltage induced on circuit interruption
-45.8 V ... -15 V
Maximum inrush current
max. 1.5 A (at nominal lamp load for 20 ms)
Output current
max. 500 mA (per channel) max. 8 A (Device)
Nominal output voltage
24 V DC
Output voltage when switched off
max. 2 V
Output current when switched off
max. 300 µA
Nominal load, inductive
12 VA (1.2 H, 48 Ω)
Nominal load, lamp
12 W
Nominal load, ohmic
12 W (48 Ω)
Maximum operating frequency with ohmic nominal load
max. 300 Hz (this switching frequency is limited by the data rate selected, the number of bus devices, the structure of the bus, the software used and the control or computer system used)
Reverse voltage resistance to short pulses
Reverse voltage proof
Behavior with overload
Auto restart
Behavior with inductive overload
Output can be destroyed
Behavior at voltage switch-off
The output follows the power supply without delay
Overcurrent shut-down
min. 0.7 A
Output current with ground connection interrupt when switched off
max. 25 mA
Product type
I/O component
Product family
Inline
Type
modular
Scope of delivery
including Inline connectors and marking fields
No. of channels
32
Operating mode
Process data operation with 2 words
Diagnostics messages
Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Article revision
09
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
2.3 W
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 140 mA (HW 00) max. 30 mA (from HW 01)
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 8 A
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logic)/functional ground
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice