Product Model

IB IL 24 DO 8-NPN

In Stock
Last updated: 2025/4/18
Phoenix Contact IB IL 24 DO 8-NPN

Selling Points

  • 1Highly Reliable Digital Output: Eight NPN transistor outputs ensure reliable digital signal transmission.
  • 2Seamless Integration: Compatible with PAC (Programmable Automation Controller) systems for easy integration into complex control architectures.
  • 3Versatile Performance: Designed to streamline automation tasks with high efficiency in demanding industrial environments.
  • 4Stringent Operational Standards: Engineered to meet stringent operational standards, ensuring durability and consistent performance.
  • 5Modular Design: Part of Bosch Rexroth's range of automation components, contributing to a modular and scalable system design.
Product Details
IB IL 24 DO 8-NPN
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
119.5 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Color
green
Connection method
Inline data jumper
Transmission speed
500 kbps
ID code (dec.)
189
ID code (hex)
BD
Length code (hex)
81
Length code (dec)
129
Process data channel
8 bit
Input address area
0 Byte
Output address area
1 Byte
Register length
8 bit
Required parameter data
3 Byte
Output name
Digital outputs
Connection method
Spring-cage connection
Connection technology
2-, 3-, 4-conductor
Number of outputs
8 (NPN)
Protective circuit
Short-circuit and overload protection
Output voltage
U
Maximum output current per channel
1 A
Maximum output current per module
8 A
Nominal output voltage
24 V DC (voltage difference at I
Nominal load, inductive
24 VA
Nominal load, lamp
24 W
Nominal load, ohmic
24 W
Behavior with overload
Auto restart
Behavior with inductive overload
Output can be destroyed
Behavior at voltage switch-off
The output follows the power supply without delay
Product type
I/O component
Product family
Inline
Type
modular
No. of channels
8
Diagnostics messages
Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 60 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 8 A
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice