Product Model
IB IL 24 DO 8-NPN-PAC

Selling Points
- 18 digital outputs for precise control in industrial automation.
- 2Compatible with 2-, 3-, and 4-conductor connection technology.
- 3Nominal current per output: 500 mA, total current: 4 A.
- 4Short-circuit and overload-protected outputs ensure reliability.
- 5Diagnostic and status indicators for easy monitoring and troubleshooting.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 48.8 mm | Height | 119.5 mm |
Depth | 71.5 mm | Note on dimensions | Housing dimensions |
EMC note | EMC: class A product, see manufacturer's declaration in the download area | No. of channels | 2 |
Connection method | Inline data jumper | Transmission speed | 500 kbps |
ID code (dec.) | 189 | ID code (hex) | BD |
Length code (hex) | 81 | Length code (dec) | 129 |
Process data channel | 8 bit | Input address area | 0 Byte |
Output address area | 1 Byte | Register length | 8 bit |
Required parameter data | 3 Byte | Required configuration data | 4 Byte |
Output name | Digital outputs | Connection method | Spring-cage connection |
Connection technology | 4-conductor | Number of outputs | 8 (NPN) |
Protective circuit | Overload protection, short-circuit protection of outputs | Output voltage | 24 V DC |
Maximum output current per channel | 1 A | Maximum output current per module | 8 A |
Nominal output voltage | 24 V DC | Nominal load, inductive | 24 VA |
Nominal load, lamp | 24 W | Nominal load, ohmic | 24 W |
Behavior with overload | Auto restart | Behavior with inductive overload | Output can be destroyed |
Behavior at voltage switch-off | The output follows the power supply without delay | Product type | I/O component |
Product family | Inline | Type | modular |
Scope of delivery | including Inline connectors and marking fields | No. of channels | 8 |
Operating mode | Process data mode with one byte | Diagnostics messages | Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module |
Overvoltage category | II (IEC 60664-1, EN 60664-1) | Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Supply voltage | 7.5 V DC (via voltage jumper) | Current draw | max. 60 mA |
Supply voltage | 24 V DC (via voltage jumper) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 8 A | Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min |
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min | Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min | Connection name | Inline connector |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Ambient temperature (operation) | -25 °C ... 55 °C | Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice