Product Model
IB IL 24 PSDI 8-PAC

Selling Points
- 1High Integrity Digital Inputs: The module provides 4 safe digital inputs for two-channel assignment or 8 safe digital inputs for single-channel assignment.
- 2Robust Safety Features: Achieve up to SIL 3 according to IEC 61508/EN 61508 and SIL CL 3 according to IEC 62061/DIN EN 62061.
- 3Flexible Transmission Speed: Set transmission speed to 500 kbaud or 2 Mbaud using a switch.
- 4Parameterizable Inputs: Inputs can be parameterized according to application for seamless integration of sensors.
- 5Durable Design: Designed with IP20 protection and suitable for ambient temperatures from -25°C to 55°C.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 48.8 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on dimensions | Housing dimensions |
Note on application | Only for industrial use | No. of channels | 2 |
Connection method | Inline data jumper | Transmission speed | 500 kbps / 2 Mbps (can be switched) |
ID code (dec.) | 163 | ID code (hex) | A3 |
Length code (hex) | 04 | Length code (dec) | 04 |
Process data channel | 8 Byte | Input address area | 8 Byte ((Operating mode: SafetyBridge)) |
Output address area | 8 Byte ((Operating mode: SafetyBridge)) | Register length | 8 Byte |
Required parameter data | 1 Byte ((Operating mode: SafetyBridge)) | Required configuration data | 5 Byte ((Operating mode: SafetyBridge)) |
Input name | Digital inputs | Description of the input | IEC 61131-2 type 3 |
Number of inputs | 4 (for 2-channel assignment)
8 (for 1-channel assignment) | Cable length | max. 200 m (200 m from the clock output to the safe input (total based on forward and return path)) |
Connection method | Spring-cage connection | Connection technology | 2-, 3-, 4-conductor |
Input voltage | 24 V DC (via clock outputs UT1 and UT2 or external supply) | Input voltage range | -3 V DC ... 30 V DC |
Input voltage range "0" signal | -3 V DC ... 5 V DC | Input voltage range "1" signal | 11 V DC ... 30 V DC |
Typical input current per channel | 4.2 mA (at 24 V) | Typical response time | See technical data |
Product type | I/O component | Product family | Inline |
Application | Functional safety | Type | modular |
Article revision | 08 | Maximum power dissipation for nominal condition | 24.12 W |
Transmission medium | Copper | Supply voltage | 7.5 V DC (see safety data) |
Current draw | max. 180 mA | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 825 mA (see safety data)
typ. 25 mA (plus current consumption of the inputs when supplied via the clock outputs, plus current consumption of the connected initiators when via through the clock outputs) |
Supply voltage | 24 V DC (via voltage jumper) | Supply voltage range | 19.2 V DC ... 30 V DC |
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min | Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min |
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min | Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min |
Connection name | Inline connector | pluggable | yes |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² | Conductor cross section AWG | 24 ... 16 |
Connection method | Spring-cage connection | Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² | Conductor cross section AWG | 24 ... 16 |
Ambient temperature (operation) | -25 °C ... 55 °C | Degree of protection | IP20 |
Air pressure (operation) | 80 kPa ... 108 kPa (up to 2000 m above sea level) | Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 70 °C | Permissible humidity (operation) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Permissible humidity (storage/transport) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice