Product Model
IB IL 24 PWR IN/2-F-D-PAC

Selling Points
- 124V DC Supply: Provides 24V DC to main and segment circuits.
- 2Fuse Protection: Internal fuse protects main and segment circuits against short circuits and overloads.
- 3Diagnostic Indicators: LED indicators show supply voltage availability and fuse status.
- 4Surge and Polarity Protection: Equipped with surge and polarity reversal protection for safe operation.
- 5Compact Design: Measures 12.2mm x 119.8mm x 71.5mm, ideal for inline stations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 12.2 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on application | Only for industrial use |
CCCex note | Use in potentially explosive areas is not permitted in China. | Number of interfaces | 2 |
Connection method | Inline data jumper | Transmission speed | 500 kbps |
ID code (dec.) | 190 | ID code (hex) | BE |
Length code (hex) | C2 | Length code (dec) | 194 |
Process data channel | 2 bit | Input address area | 2 bit |
Output address area | 0 bit | Register length | 2 bit |
Required parameter data | 1 Byte | Required configuration data | 4 Byte |
Product type | I/O component | Product family | Inline |
Type | modular | Number of plugs | 1 |
Operating mode | Process data mode with 2 bits | Special properties | 24 V DC
U
With fuse (U
With diagnostics |
Article revision | 08 | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Maximum power dissipation for nominal condition | 0.7 W | Test section | 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min
7.5 V supply (bus logic)/functional ground 500 V AC 50 Hz 1 min |
Protective circuit | Surge protection; Suppressor diode
Reverse polarity protection; Parallel polarity protection diode
Overload protection, short-circuit protection in the main and segment circuits; Fuse 5x20 with 6.3 A slow-blowFuses with other values can also be used. The maximum fuse value is 6.3 A.For fuses with a value greater than 2 A, only slow-blow fuses may be used. | Fuse | SI 5 x 20 6, 300 AT (in scope of delivery) |
I/O voltage | 24 V DC | I/O voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Residual ripple | ± ±5 % | Max. current consumption | 4 A |
Typical current consumption | 30 mA | Supply voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 25 mA | Power consumption | max. 0.19 W |
Supply voltage | 24 V DC (via Inline connector) | Supply voltage range | 19.2 V ... 30 V (including all tolerances, including ripple) |
Current draw | typ. 4 A (nominal value) | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | typ. 4 A (nominal value) |
Connection name | Inline connector | Connection method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Connection method | Spring-cage connection | Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 55 °C | Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) | Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice