Product Model
IB IL 24 PWR IN/R-PAC

Selling Points
- 1Provides 24 V DC supply for various applications.
- 2Equipped with surge protection for segment, main, and 24 V supplies.
- 3Constructed for use in potentially explosive areas with a maximum current of 8 A.
- 4Includes diagnostics displays for monitoring and status indicators.
- 5Supports inline data jumper and inline local bus interfaces.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 48.8 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on application | Only for industrial use |
CCCex note | Use in potentially explosive areas is not permitted in China. | Number of interfaces | 2 |
Connection method | Inline data jumper | Transmission speed | 500 kbps / 2 Mbps (Can be used in Inline stations with these transmission speeds) |
ID code (dec.) | none | ID code (hex) | none |
Register length | 0 bit | Required parameter data | 0 Byte |
Required configuration data | 0 Byte | Product type | I/O component |
Product family | Inline | Type | modular |
Number of plugs | 4 | Special properties | 24 V DC
Supply/boost U |
Article revision | 11 | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Maximum power dissipation for nominal condition | 3 W | Test section | 7.5 V communications power, 24 V analog supply/functional ground 500 V AC 50 Hz 1 min
7.5 V logics supply, 24 V analog supply / 24 V main supply, 24 V segment supply 500 V AC 50 Hz 1 min
24 V main supply, 24 V segment supply/functional ground 500 V AC 50 Hz 1 min |
Protective circuit | Surge protection (segment supply, main supply, 24 V supply); Input protective diodes (can be destroyed by permanent overload)Pulse loads up to 1500 W are short circuited by the input protective diode.
Protection against polarity reversal (segment supply/main supply); Parallel diodes for protection against polarity reversal; in the event of an error the high current flowing through the diodes causes the fuse connected upstream to blow.
Polarity reversal (24 V supply); Serial diode in the lead path of the power supply unit; in the event of an error only a low current flows. In the event of an error, no fuse trips within the external power supply unit. | Fuse | electrical/thermal overload protection, included in scope of delivery |
I/O voltage | 24 V DC | I/O voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Residual ripple | ± 1.2 V | Max. current consumption | 8 A |
Supply voltage | 24 V DC (via Inline connector) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 1.25 A DC (at nominal voltage; consisting of: 0.75 A DC for the communications power and 0.5 A DC for the analog voltage supply)
min. 12 mA DC (at nominal voltage) | Supply voltage | 7.5 V DC (via voltage jumper) |
Supply voltage | 24 V DC | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Supply voltage | 24 V DC (via Inline connector) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Supply voltage | 24 V DC (via Inline connector) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Connection name | Inline connector | Connection method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Connection method | Spring-cage connection | Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 55 °C | Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) | Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice