Product Model
IB IL 24 SEG-ELF

Selling Points
- 1Monitor segment circuit status with LED diagnostics.
- 2Safeguard your circuit with short-circuit current limitation.
- 3Easy installation on DIN rail for compact and organized setups.
- 4Operate at 24 V DC with a voltage range of 19.2 V to 30 V DC.
- 5Ensure circuit integrity with built-in overload protection.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Type | modular | Number of plugs | 1 |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | Error messages via the bus | Short-circuit/Overload in segment circuit
Operating voltage fallen below or exceeded |
ID code (dec.) | 190 | ID code (hex) | BE |
Length code (hex) | C2 | Length code (dec) | 194 |
Process data channel | 2 bit | Input address area | 2 bit |
Output address area | 0 bit | Register length | 2 bit |
Required parameter data | 1 Byte | Test section | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min |
Protective circuit | Overload protection | Fuse | 2.5 A (electronic) |
I/O voltage | 24 V DC | I/O voltage range | 19.2 V DC ... 30 V DC |
Residual ripple | ± 1.2 V | Max. current consumption | 2.5 A |
Typical current consumption | 30 mA | Supply voltage | 7.5 V DC |
Current draw | 30 mA DC (maximum) | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 2.5 A (nominal value) |
Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Connection method | Inline potential distributor |
Connection method | Inline data jumper | Width | 12.2 mm |
Height | 119.8 mm | Depth | 71.5 mm |
Color | green | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 55 °C | Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 75 % ... 85 % (in the range of -25°C ... +55°C, appropriate measures against increased humidity (> 85%) must be taken.) | Permissible humidity (storage/transport) | 75 % ... 85 % (Slight temporary condensation may sometimes appear on the housing, e.g. when the terminal block is brought out of a vehicle into an enclosed room.) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice