Product Model
IB IL 24 SEG/F-XC-PAC

Selling Points
- 1Creates a protected partial circuit (segment circuit) within an Inline station.
- 2Operates in extreme ambient temperatures (-40°C to 70°C) and humidity levels (10% to 95%).
- 3Equipped with a 6.3 A slow-blow fuse for overload and short-circuit protection.
- 4Meets IP20 standards for dust and water protection.
- 5Supports 24V DC supply with a range of 19.2V to 30V DC and includes an inline potential distributor.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 12.2 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on application | Only for industrial use |
Number of interfaces | 2 | Connection method | Inline data jumper |
Transmission speed | 500 kbps / 2 Mbps (Can be used in Inline stations with these transmission speeds) | ID code (dec.) | none |
ID code (hex) | none | Register length | 0 bit |
Required parameter data | 0 Byte | Required configuration data | 0 Byte |
Product type | I/O component | Product family | Inline |
Type | modular | Article revision | 02 |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | Maximum power dissipation for nominal condition | 0 W |
Test section | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min | Protective circuit | Overload protection, short-circuit protection in the segment circuit; Fuse 5 x 20 with 6.3 A, slow-blowFuses with other values can also be used. The maximum fuse value is 8 A.For fuses with a value greater than 2 A, only slow-blow fuses may be used.
Surge protection; Protective elements in the power terminal or the bus coupler
Reverse polarity protection; Protective elements in the power terminal or the bus coupler |
Fuse | SI 5 x 20 6, 300 AT (in scope of delivery) | Communications power U | 7.5 V DC |
Supply voltage | 24 V DC | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 8 A (nominal value)
typ. 6 A (The terminal is supplied with a 6.3 A slow-blow fuse. In the event of an increased total current in the potential jumpers U | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Connection name | Inline connector |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 55 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) | Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | GRP_Temperature class | T2 (-40 °C ... 55 °C, EN 50155) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice