Product Model
IB IL 400 ELR R-3A

Selling Points
- 1Integrated electronic motor protection in accordance with IEC 60947-4.
- 2Motor current monitoring and parameterization via INTERBUS.
- 3Hand-held operator panel mode for easy control and diagnostics.
- 4Connection option for an external passive brake module.
- 5Compact dimensions: 63 mm width, 224 mm height, and 109 mm depth.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 63 mm | Height | 224 mm |
Depth | 109 mm | Number of interfaces | 2 |
Connection method | Inline data jumper | Transmission speed | 500 kbps |
Transmission physics | Copper | ID code (dec.) | 191 |
ID code (hex) | BF | Length code (hex) | 81 |
Length code (dec) | 129 | Process data channel | 8 bit |
Input address area | 1 Byte | Output address area | 1 Byte |
Register length | 1 Byte | Required parameter data | 5 Byte |
Required configuration data | 5 Byte | Product type | I/O component |
Product family | Inline | Type | modular |
Mounting position | Panel mounting on horizontal DIN rail | Operating mode | Process data mode with one byte |
Diagnostics messages | Overcurrent Error message in the diagnostic code (bus) and display via the LED ERR on the module
Output stage cannot be controlled Error message in the diagnostic code (bus) and display via the LED ERR on the module | Power consumption | max. 1.2 W (entire device) |
Supply voltage | 7.5 V DC (via voltage jumper) | Current draw | max. 45 mA |
Power consumption | max. 0.34 W | Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC ... 28.8 V DC (including all tolerances, including ripple) | Current draw | max. 50 mA |
Test voltage: Supply voltage U | 1.2 kV AC, 50 Hz, 1 min | Test voltage: Supply voltage U | 1.2 kV AC, 50 Hz, 1 min |
Test voltage: Supply voltage U | 1.2 kV AC, 50 Hz, 1 min | Test voltage: Supply voltage U | 1.2 kV AC, 50 Hz, 1 min |
Test voltage: Local bus/400 V level | 1.2 kV AC, 50 Hz, 1 min | Test voltage: Local bus/Brake control switch | 1.2 kV AC, 50 Hz, 1 min |
Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 55 °C |
Note | Notes on operation Line protection for the network supply line, max. 20 A. Observe derating of the POWER-COMBICON connector | Air pressure (operation) | 70 kPa ... 106 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 85 % (non-condensing) | Permissible humidity (storage/transport) | 10 % ... 85 % (non-condensing) |
Protection class | I (IEC 61140, EN 61140, VDE 0140-1) | Mounting type | DIN rail mounting |
Assembly note | To safeguard sufficient ventilation, ensure that there is an installation clearance of a minimum of 50 cm both above and below. | Mounting position | Panel mounting on horizontal DIN rail |
Specifications may be subject to change without notice