Product Model

IB IL AI 2-HART

In Stock
Last updated: 2025/4/19
Phoenix Contact IB IL AI 2-HART

Selling Points

  • 1Advanced Analog Input: Supports two differential signal inputs for current sensors with 4 mA to 20 mA and 0 mA to 25 mA ranges.
  • 2HART Protocol Support: Enables bidirectional communication with smart field devices using the standardized HART protocol.
  • 3Robust Connectivity: Offers point-to-point and multi-drop connections, as well as the connection of a hand-held operating panel.
  • 4High Resolution Measurement: Acquires measured values with a resolution of 16 bits, providing precise process information.
  • 5Compact Design: Designed for inline stations with a compact size (48.8 mm x 135 mm x 71.5 mm) and IP20 degree of protection.
Product Details
IB IL AI 2-HART
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Type
modular Inline
ID code (dec.)
220
ID code (hex)
DC
Length code (hex)
02
Length code (dec)
02
Process data channel
32 bit
Input address area
4 Byte
Output address area
4 Byte
Register length
64 bit
Required parameter data
9 Byte
Required configuration data
5 Byte
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 110 mA typ. 95 mA
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 150 mA typ. 50 mA
Input name
Analog inputs
Number of inputs
max. 2 (Differential inputs, current)
A/D conversion time
approx. 10 µs (bus-synchronous)
Connection technology
2-conductor (shielded)
Current input signal
4 mA ... 20 mA 0 mA ... 25 mA
Data formats
IL, standardized representation
Limit frequency (3 dB)
25 Hz
Measuring principle
Successive approximation
Measured value resolution
16 bits (15 bits + sign bit)
Measured value representation
16 bit two's complement
Input resistance current input
250 Ω
Number of inputs
2 (Differential inputs, current)
Current input signal
4 mA ... 20 mA 0 mA ... 25 mA
Input resistance current input
250 Ω
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
No. of channels
2
Connection method
Inline data jumper
Transmission speed
500 kbps
Transmission physics
Copper
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Color
green
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice