Product Model

IB IL AI 4/EF

In Stock
Last updated: 2025/4/19
Phoenix Contact IB IL AI 4/EF

Selling Points

  • 1High-Speed Signal Acquisition: Short update time of 1 ms for all channels.
  • 2Integrated Protection: Channel-specific integrated short-circuit and overload protection.
  • 3Diverse Signal Ranges: Supports 0 - 20 mA, 4 - 20 mA, ±20 mA, 0 - 10 V, ±10 V, and 0 - 5 V ±5 V.
  • 4High Resolution: Measured value acquisition with 16-bit resolution.
  • 5Versatile Connectivity: Connection of sensors in 2, 3, or 4-wire technology.
Product Details
IB IL AI 4/EF
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Type
modular Inline
ID code (dec.)
223
ID code (hex)
DF
Length code (hex)
05
Length code (dec)
05
Input address area
10 Byte
Output address area
10 Byte
Register length
96 bit
Required parameter data
28 Byte
Required configuration data
4 Byte
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 100 mA typ. 85 mA
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 20 mA typ. 13 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 200 mA
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logic), 24 V supply U
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logic), 24 V supply U
500 V AC, 50 Hz, 1 min
Test voltage: I/O/functional ground
500 V AC, 50 Hz, 1 min
Input name
Analog inputs
Description of the input
Differential input, including sensor supply (24 V DC)
Number of inputs
max. 4
A/D conversion time
max. 10 µs
Connection method
Inline shield connector
Connection technology
2-, 3-, 4-conductor (shielded)
Current input signal
0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA
Voltage input signal
0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V
Data formats
IB IL, IB ST, standardized representation, S7 compatible
Limit frequency (3 dB)
500 Hz
Measured value resolution
16 bits (15 bits + sign bit)
Protective circuit
Transient protection; Yes, via arresters
Number of inputs
4 (differential inputs, voltage)
A/D converter resolution
15 bit
Voltage input signal
0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V
Input resistance of voltage input
300 kΩ
Measured value resolution
16 bits (15 bits + sign bit)
Number of inputs
4 (Differential inputs, current)
Current input signal
0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA
Input resistance current input
approx. 110 Ω
Protective circuit
Overload protection
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
Inline data jumper
Transmission speed
500 kbps
Transmission physics
Copper
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Color
green
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice