Product Model

IB IL AI 8/SF-2MBD

In Stock
Last updated: 2025/4/27
Phoenix Contact IB IL AI 8/SF-2MBD

Selling Points

  • 1High Accuracy Analog Input Terminal: Designed for precise acquisition of analog voltage and current signals.
  • 28 Single-Ended Inputs: Connects either voltage or current signals with 8 independent analog inputs.
  • 3High Measuring Accuracy: Ensures reliable data with a 16-bit analog/digital converter.
  • 4Fast Transmission Speed: Supports a local bus transmission speed of 2 Mbps for efficient data transfer.
  • 5IP20 Protection: Offers a degree of protection IP20, suitable for various industrial applications.
Product Details
IB IL AI 8/SF-2MBD
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Color
green
No. of channels
8
Connection method
Inline data jumper
Transmission speed
2 Mbps
Transmission physics
Copper
ID code (dec.)
95
ID code (hex)
5F
Length code (hex)
02
Length code (dec)
02
Process data channel
32 bit
Input address area
4 Byte
Output address area
4 Byte
Register length
32 bit
Required parameter data
6 Byte
Input name
Analog inputs
Number of inputs
max. 8 (single ended)
A/D conversion time
approx. 10 µs
Connection technology
2-conductor (shielded)
Current input signal
0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA 0 mA ... 40 mA -40 mA ... 40 mA
Voltage input signal
0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V 0 V ... 25 V -25 V ... 25 V 0 V ... 50 V
Data formats
IB IL, IB ST, IB RT, standardized representation, PIO format
Limit frequency (3 dB)
3.5 kHz
Measuring principle
Successive approximation
Measured value resolution
16 bits (15 bits + sign bit)
Measured value representation
16 bit two's complement
Number of inputs
8 (Single-ended voltage inputs)
Voltage input signal
0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V 0 V ... 25 V -25 V ... 25 V 0 V ... 50 V
Input resistance of voltage input
> 240 kΩ 0.01 %
Number of inputs
8 (single-ended current inputs)
Current input signal
0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA 0 mA ... 40 mA -40 mA ... 40 mA
Input resistance current input
25 Ω 0.01 %
Product type
I/O component
Type
modular Inline
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 85 mA typ. 68 mA
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 38 mA typ. 24 mA
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logic), 24 V supply U
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logic), 24 V supply U
500 V AC, 50 Hz, 1 min
Test voltage: I/O/functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice