Product Model

IB IL CNT-PAC/CN

In Stock
Last updated: 2025/4/18
Phoenix Contact IB IL CNT-PAC/CN

Selling Points

  • 1Freely Parameterizable Switching Output: Independently set switching output for fast response times.
  • 2Multiple Operating Modes: Supports event counting, time or state-controlled frequency measurement, time measurement, and pulse generation.
  • 3High Input Frequency: Processes signals up to 100 kHz for precise measurements.
  • 4Robust Design: Operates in a wide ambient temperature range (-25 °C to 55 °C) and humidity (10% to 95% non-condensing).
  • 5Versatile Signal Processing: Handles both 5 V and 24 V signals with 16-bit counter value for time measurement and 24-bit counter value for event counting and frequency measurement.
Product Details
IB IL CNT-PAC/CN
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
24.4 mm
Height
135 mm
Depth
71.5 mm
Connection method
Inline data jumper
Transmission speed
500 kbps
Transmission physics
Copper
ID code (dec.)
191
ID code (hex)
BF
Length code (hex)
02
Length code (dec)
02
Process data channel
32 bit
Input address area
4 Byte
Output address area
4 Byte
Register length
4 Byte
Required parameter data
1 Byte
Required configuration data
5 Byte
Input name
Counter input for 24 V signals
Connection method
Spring-cage connection
Connection technology
2-, 3-conductor
Number of inputs
1 (only one counter input can be used, either for 24 V or for 5 V signals)
Operating mode
Event counting, frequency/time measurement
Input voltage
24 V DC (Nominal voltage) 30 V DC (maximum)
Input voltage range "0" signal
0 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Input frequency
max. 100 kHz
Input current
typ. 5 mA
Input resistance
approx. 5.7 kΩ
Input name
Counter input for 5 V signals
Connection method
Spring-cage connection
Connection technology
2-conductor (shielded), external 5 V supply
Number of inputs
1 (only one counter input can be used, either for 24 V or for 5 V signals)
Operating mode
Event counting, frequency/time measurement
Input voltage
5 V DC (Nominal voltage) 8 V DC (maximum)
Input voltage range "0" signal
0 V ... 1.5 V
Input voltage range "1" signal
3.5 V ... 8 V
Input frequency
max. 100 kHz
Input current
typ. 5 mA
Input resistance
approx. 1.7 kΩ
Output name
Switching output
Connection method
Spring-cage connection
Connection technology
2-conductor
Number of outputs
1
Protective circuit
Short-circuit protection; Yes, short-circuit-proof (automatically switched on again) Overload protection
Output voltage
24 V DC (Nominal voltage)
Output current
max. 0.5 A (Nominal current)
Nominal load, inductive
max. 12 VA (1.2 H, 48 Ω)
Nominal load, lamp
max. 12 W
Nominal load, ohmic
max. 12 W (48 Ω)
Reverse voltage resistance to short pulses
Reverse voltage proof
Behavior in the event of ohmic overload
Auto restart after eliminating the overload
Behavior with inductive overload
Output can be destroyed
Behavior in the event of lamp overload
Auto restart after eliminating the overload
Overcurrent shut-down
min. 0.7 A
Product type
I/O component
Type
modular Inline
Operating mode
Process data operation with 2 words
Diagnostics messages
Sensor supply short-circuit Sensor supply overload
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 50 mA typ. 40 mA
Power consumption
max. 0.375 W (at U
Supply voltage
24 V DC (via voltage jumper)
Current draw
max. 1 A
Designation
Power supply for sensors
Supply voltage
24 V DC (generated from segment supply U
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice