Product Model

IB IL DO 4 AC-1A

In Stock
Last updated: 2025/4/17
Phoenix Contact IB IL DO 4 AC-1A

Selling Points

  • 1Output digital signals in the AC voltage range with four reliable digital outputs.
  • 2Connect actuators using the efficient 3-wire technology for seamless integration.
  • 3Monitor terminal status with diagnostic and status indicators for easy troubleshooting.
  • 4Handle a total current of 4 A with each output capable of 1 A, ensuring robust performance.
  • 5Meets EMC class A standards and has IP20 degree of protection for safe operation in various environments.
Product Details
IB IL DO 4 AC-1A
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Color
gray
Connection method
Inline data jumper
Transmission speed
500 kbps
ID code (dec.)
189
ID code (hex)
BD
Length code (hex)
41
Length code (dec)
65
Process data channel
4 bit
Input address area
0 Byte
Output address area
4 bit
Register length
4 bit
Required parameter data
3 Byte
Output name
Digital outputs
Connection method
Spring-cage connection
Connection technology
3-conductor
Number of outputs
4
Protective circuit
Overload protection, short-circuit protection of outputs
Maximum output current per channel
1 A
Maximum output current per module
4 A
Nominal output voltage
230 V AC
Output voltage range
12 V AC ... 253 V AC (via voltage jumper)
Product type
I/O component
Product family
Inline
Type
modular
No. of channels
4
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 45 mA
Supply voltage
230 V AC (via voltage jumper)
Current draw
max. 4 A
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics) / I/O area
2500 V AC, 50 Hz, 1 min
Test voltage: Routine test
1200 V AC, 50 Hz, 1 min
Test voltage: I/O area / FE
500 V AC, 50 Hz, 1 min
Test voltage: Output / Phase
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
75 % ... 85 % (in the range of -25°C ... +55°C, appropriate measures against increased humidity (> 85%) must be taken.)
Permissible humidity (storage/transport)
75 % ... 85 % (slight temporary condensation may sometimes appear on the housing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice