Product Model
IB IL INC-IN-2MBD-PAC

Selling Points
- 1Supports both symmetrical (RS-422) and asymmetrical (5 V DC to 24 V DC) incremental encoders.
- 2Includes three digital 24 V DC inputs for limit position switches and home position switch.
- 3Monitors encoder inputs for broken cables to ensure operational safety.
- 4Offers precise evaluation via 1x, 2x, or 4x sampling with a maximum input frequency of 300 kHz.
- 5Provides a direction of rotation indicator via LED for easy monitoring.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 24.4 mm | Height | 140.5 mm |
Depth | 71.5 mm | Note on application | Only for industrial use |
Number of interfaces | 2 | Connection method | Inline data jumper |
Transmission speed | 2 Mbps | Transmission physics | Copper |
ID code (dec.) | 127 | ID code (hex) | 7F |
Length code (hex) | 02 | Length code (dec) | 02 |
Process data channel | 32 bit | Input address area | 4 Byte |
Output address area | 4 Byte | Register length | 4 Byte |
Required parameter data | 1 Byte | Required configuration data | 5 Byte |
Input name | Digital inputs | Description of the input | EN 61131-2 type 1 |
Number of inputs | 3 | Connection method | Spring-cage connection |
Connection technology | 3-conductor | Input voltage range "0" signal | -3 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC | Nominal input voltage U | 24 V DC |
Nominal input current at U | typ. 2.7 mA | Number of inputs | 1 (Symmetrical or asymmetrical) |
Input name | Incremental encoder input | Encoder signals | symmetrical encoders according to EIA-422 and asymmetrical encoders |
Cable length | max. 30 m (shielded cable, to ensure conformance with EMC Directive) | Output name | Digital outputs |
Connection method | Spring-cage connection | Connection technology | 2-conductor |
Number of outputs | 1 (NPN, double assignment of input E3) | Product type | I/O component |
Product family | Inline | Type | modular |
Scope of delivery | including Inline connectors and marking fields | Operating mode | Process data mode with two words |
Overvoltage category | II (IEC 60664-1, EN 60664-1) | Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Maximum power dissipation for nominal condition | 1.4 W | Number | 1 |
Nominal output voltage | 5 V DC | Voltage range | 4.75 V DC ... 5.25 V DC |
Current carrying capacity | max. 250 mA | Protective circuit | Short-circuit protection; Electrical and thermal |
Number | 1 | Nominal output voltage | 24 V DC |
Voltage range | 19.2 V DC ... 30 V DC | Current carrying capacity | max. 250 mA |
Protective circuit | Short-circuit protection; Electronic and thermal | Number | max. 1 (A, /A, B, /B, Z, /Z) |
Designation | Symmetrical incremental encoders | Encoder supply voltage | 5 V DC
24 V DC |
Signal voltage level | Differential signal (signal – inverted signal) ±0.5 V, minimum; ±6 V, maximum | Common mode voltage range signal - ground | -10 V DC ... 13.2 V DC |
Input frequency | max. 300 kHz | Number | max. 1 (A, B, (Z)) |
Designation | Asymmetrical incremental encoder | Encoder supply voltage | 5 V DC
24 V DC |
Signal voltage level | Low ≤ 2.5 V, high ≥ 3.5 V (up to 27 V, maximum) | Input frequency | max. 300 kHz |
Supply voltage | 7.5 V (via voltage jumper) | Current draw | max. 80 mA |
Supply voltage | 24 V DC (via voltage jumper) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 1 A
typ. 340 mA | Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min | Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 500 min |
Connection name | Inline connector | Connection method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Connection method | Spring-cage connection | Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Ambient temperature (operation) | -25 °C ... 55 °C |
Degree of protection | IP20 | Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) | Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | Mounting type | DIN rail mounting |
Specifications may be subject to change without notice