Product Model

IB IL PM 3P/N/EF-PAC

In Stock
Last updated: 2025/4/25
Phoenix Contact IB IL PM 3P/N/EF-PAC

Selling Points

  • 1Direct measurement of AC currents up to 5A, including neutral conductor currents.
  • 2Supports phase conductor voltages up to 690V AC for phase/phase connections.
  • 3Freely definable measurement intervals for precise data collection.
  • 4Includes harmonics analysis and determination of maximum values.
  • 5Equipped with an operating hours counter and power meter for comprehensive monitoring.
Product Details
IB IL PM 3P/N/EF-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Note on application
Only for industrial use
Number of interfaces
2
Connection method
Inline data jumper
Transmission speed
500 kbps
ID code (dec.)
220
ID code (hex)
DC
Length code (hex)
0C
Length code (dec)
12
Process data channel
192 bit
Input address area
24 Byte
Output address area
24 Byte
Register length
28 Byte
Required parameter data
29 Byte
Required configuration data
5 Byte
Product type
I/O component
Product family
Inline
Type
modular
Operating mode
Process data mode with 12 words, PCP with 2 words
Diagnostics messages
Two line conductors confused I/O error message One line conductor not connected or wire break at line conductor I/O error message Measuring circuit fault I/O error message Value range for transformer factors exceeded I/O error message Value range for other settings exceeded I/O error message
Article revision
08
Overvoltage category
III (up to 300 V), II (up to 400 V)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
2.7 W
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
typ. 130 mA
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.2 mm² ... 1.5 mm²
Conductor cross section flexible
0.2 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.2 mm² ... 1.5 mm²
Conductor cross section, flexible
0.2 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
80 kPa ... 106 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
80 kPa ... 106 kPa (up to 2000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
II (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice