Product Model

IB IL PWM/2

In Stock
Last updated: 2025/4/19
Phoenix Contact IB IL PWM/2

Selling Points

  • 1Control multiple outputs independently with two separate channels.
  • 2Set period lengths from 100 µs to 10 s and duty factors in 0.39% increments.
  • 3Generate frequencies between 0 Hz and 50 kHz for precise control.
  • 4Set pulse lengths from 10 µs to 25.5 s for precise timing.
  • 5Operate at 5 V or 24 V for versatility in various applications.
Product Details
IB IL PWM/2
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Type
modular
Number of plugs
2
Operating mode
Process data operation with 2 words
Error messages via the bus
Short-circuit or overload of the output
ID code (dec.)
191
ID code (hex)
BF
Register length
32 bit
Required parameter data
1 Byte
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min 24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min
I/O voltage
24 V DC (via voltage jumper)
I/O voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Residual ripple
5 %
Typical current consumption
approx. 100 mA
Number of inputs
0
Output voltage
5 V DC
Output current
10 mA (5 V) 500 mA (24 V)
Number of outputs
2
Output voltage
24 V
Maximum switching voltage
24 V (to segment circuit)
Output voltage
5 V
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
Inline data jumper
Transmission speed
500 kbps
Transmission physics
Copper
Width
24.4 mm
Height
119.8 mm
Depth
71.5 mm
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
75 % ... 85 % (in the range of -25°C ... +55°C, appropriate measures against increased humidity (> 85%) must be taken.)
Permissible humidity (storage/transport)
75 % ... 85 % (Slight temporary condensation may sometimes appear on the housing, e.g. when the terminal block is brought out of a vehicle into an enclosed room.)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice