Product Model
IB IL SAFE 2-ECO

Selling Points
- 14 inputs for 2 sensor circuits (1- or 2-channel, non-equivalent/equivalent).
- 2Approved for 0°C to +55°C.
- 3Compact and efficient inline terminal design.
- 4100% genuine product, no counterfeits or tampering.
- 5Available with discounted pricing for bulk orders and projects.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 24.4 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on dimensions | Housing dimensions |
Connection method | Inline data jumper | Transmission speed | 500 kbps |
ID code (dec.) | 190 | ID code (hex) | BE |
Length code (hex) | 41 | Length code (dec) | 65 |
Process data channel | 4 bit | Input address area | 4 bit |
Output address area | 0 bit | Register length | 4 bit |
Required parameter data | 1 Byte | Required configuration data | 4 Byte |
Input name | Digital inputs | Description of the input | IEC 61131-2 type 3 |
Number of inputs | 4 (for 2 sensor circuits (1- or 2-channel, non-equivalent/equivalent)) | Connection method | Spring-cage connection |
Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off; at inputs 1.2, 1.3, 3.2, 3.3)
0 V DC ... 5 V DC (at inputs 2.3, 4.3) | Input voltage range "1" signal | 11 V DC ... 30 V DC (at inputs 1.2, 1.3, 2.3, 3.2, 3.3, 4.3)
19.2 V DC ... 30 V DC (at inputs 3.4, 4.4) |
Protective circuit | Surge voltage; Suppressor diode
Reverse polarity protection | Number of outputs | 1 (internal, 2-channel enabling current path) |
Contact switching type | N/O contact | Switching current | min. 3 mA
min. 6 A (30 V DC) |
Switching capacity | min. 60 mW | Min. switching current | min. |
Max. switching current | min. | Limiting continuous current | 6 A (observe derating) |
Mechanical service life | 10 | Output fuse | 6 A gL/gG (See “Application examples” section) |
Product type | I/O component | Product family | Inline |
Application | Functional safety | Type | modular |
Mounting position | vertical or horizontal | Scope of delivery | including Inline connectors and marking fields |
Operating mode | Process data operation with 4 bits
Process data operation with 4 bits | Special properties | for safety-related shutdown of the segment voltage by means of potential routing |
Article revision | 02 | Overvoltage category | III |
Pollution degree | 2 (in accordance with EN 50178) | Typical response time | < 100 ms (manual, monitored start)
< 150 ms (automatic start) |
Typical release time | < 30 ms (when actuation is via the sensor circuit) | Restart time | < 1 s (Boot time) |
Recovery time | < 500 ms | Maximum power dissipation for nominal condition | 4.7 W (at U |
Supply voltage | 7.5 V DC | Current draw | max. 35 mA |
Supply voltage | 24 V DC -20 % / +15 % | Current draw | typ. 70 mA |
Supply voltage | 24 V DC (via voltage jumper) | Supply voltage range | 19.2 V DC ... 30 V DC |
Connection name | Inline connector | Connection method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Connection method | Spring-cage connection | Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Ambient temperature (operation) | 0 °C ... 55 °C (observe derating) |
Degree of protection | IP20 | Degree of protection at installation location | min. IP54 |
Ambient temperature (storage/transport) | -25 °C ... 70 °C | Air clearances and creepage distances | EN 50178 |
Mounting type | DIN rail mounting | Assembly note | See derating curve |
Mounting position | vertical or horizontal |
Specifications may be subject to change without notice