Product Model

IB IL SGI 2/F-2MBD-PAC

In Stock
Last updated: 2025/4/18
Phoenix Contact IB IL SGI 2/F-2MBD-PAC

Selling Points

  • 1Fast Inputs for Strain Gauges: Equipped with 2 quick inputs for strain gauges.
  • 26- and 4-Wire Connection: Supports both 6- and 4-wire connection methods for strain gauges.
  • 3Sensor Supply Voltage: Provides sensor supply voltage, eliminating the need for an external power supply.
  • 4Process Data Operation: Communicates via process data or parameter channel (PCP) for efficient data transfer.
  • 5Diagnostic Indicators: Features diagnostic and status indicators for easy monitoring and troubleshooting.
Product Details
IB IL SGI 2/F-2MBD-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
136 mm
Depth
71.5 mm
Note on application
Only for industrial use
Number of interfaces
2
Connection method
Inline data jumper
Transmission speed
2 Mbps
Transmission physics
Copper
ID code (dec.)
223
ID code (hex)
DF
Length code (hex)
03
Length code (dec)
03
Process data channel
48 bit
Input address area
6 Byte
Output address area
6 Byte
Register length
32 bit
Required parameter data
15 Byte
Required configuration data
5 Byte
Description of the input
Input channels for strain gauge
Number of inputs
2
Connection technology
6 or 4-wire, twisted pair shielded cable
Bridge difference U
Measuring range specified by selecting the characteristic and the bridge voltage
Bridge voltage U
3.3 V 5 V
Measured value representation
15 bit + sign bit
Characteristics
±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V +1 mV/V, +2 mV/V, +3 mV/V, +4 mV/V
Output description
Voltage output
Number of outputs
2
Impedance
> 58.3 Ω (typical; permissible total resistance of the strain gauge)
Output voltage
5 V 3.3 V
Output current
typ. 55 mA (with U typ. 85 mA (with U
Product type
I/O component
Product family
Inline
Type
modular
Scope of delivery
including Inline connectors and marking fields
Operating mode
Process data operation with 3 words, PCP with 1 word
Special properties
2 fast inputs 4-, 6-conductor connection technology
Diagnostics messages
Failure of the power supply at U Failure of or insufficient communications power U I/O error Error message in the process data
Article revision
07
Maximum power dissipation for nominal condition
1.25 W
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 110 mA typ. 100 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
typ. 32 mA (with maximum load of 58.3 Ω when U typ. 8 mA (without strain gauge)
Test voltage: Logic/analog I/O (digital isolator)
500 V AC, 50 Hz, 1 min
Test voltage: Functional ground/analog I/O (isolating distance)
500 V AC, 50 Hz, 1 min
Test voltage: Logic/functional ground (isolating distance)
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice