Product Model

IB IL TEMP 2 RTD-PAC

In Stock
Last updated: 2025/4/17
Phoenix Contact IB IL TEMP 2 RTD-PAC

Selling Points

  • 1Accurate Temperature Measurement: Measures signals from conventional thermocouples and resistance thermometers with 16-bit resolution.
  • 2Versatile Sensor Compatibility: Supports Pt, Ni, KTY, and Cu sensors according to DIN and SAMA standards.
  • 3Configurable Sensor Curves: User-configurable sensor characteristic curves for optimal adaptation in various applications.
  • 4Robust Construction: Designed for industrial use with a robust construction and high reliability.
  • 5Easy Labeling and Connection: Features hinged labeling fields and spring-cage connections for easy setup and labeling.
Product Details
IB IL TEMP 2 RTD-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
12.2 mm
Height
136.8 mm
Depth
71.5 mm
Note on application
Only for industrial use
CCCex note
Use in potentially explosive areas is not permitted in China.
Number of interfaces
2
Connection method
Inline data jumper
Transmission speed
500 kbps
ID code (dec.)
127
ID code (hex)
7F
Length code (hex)
02
Length code (dec)
02
Process data channel
32 bit
Input address area
4 Byte
Output address area
4 Byte
Register length
32 bit
Required parameter data
6 Byte
Required configuration data
4 Byte
Input name
Analog RTD inputs
Description of the input
Input for resistive temperature sensors
Number of inputs
2
Connection method
Spring-cage connection
Connection technology
2-, 3-, 4-conductor
Note regarding the connection technology
shielded
A/D conversion time
typ. 120 µs (per channel)
A/D converter resolution
16 bit
Sensor types (RTD) that can be used
Pt, Ni, KTY, Cu sensors, linear resistors
Measuring principle
Successive approximation
Measured value representation
16 bit two's complement
Linear resistance measuring range
0 Ω ... 400 Ω 0 Ω ... 4 kΩ
Process data update
32 ms (both channels use 3-conductor technology) 20 ms (one channel in 2-conductor technology and one channel in 4-conductor technology) 20 ms (both channels in 2-conductor technology)
Product type
I/O component
Product family
Inline
Type
modular
Scope of delivery
including Inline connector and labeling field
Operating mode
Process data operation with 2 words
Diagnostics messages
Failure of the internal I/O supply I/O error message sent to the bus coupler Failure of or insufficient communications power U I/O error Error message in the process data User error Error message in the process data
Article revision
11
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
0.9 W
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 60 mA typ. 43 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 18 mA typ. 11 mA
Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logic)/functional ground
500 V AC, 50 Hz, 1 min
Test voltage: 24 V analog supply (analog I/O)/functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice