Product Model
IB IL TEMP 2 UTH/CG-PAC

Selling Points
- 1High Accuracy Measurement: Measures signals from conventional thermocouples and resistance thermometers with 16-bit resolution.
- 2Configurable Temperature Measurement: Supports absolute and differential temperature measurement, configurable for various applications.
- 3Versatile Sensor Compatibility: Compatible with U, T, L, J, E, K, N, S, R, B, C, W, HK thermocouples.
- 4Durable Design: Operates in ambient temperatures from -25°C to 55°C and up to 95% humidity.
- 5Easy Installation: Includes accessories like labeling fields and inline shield connectors for easy setup and customization.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
EMC note | EMC: class A product, see manufacturer's declaration in the download area | Color | green |
Connection method | Inline data jumper | Transmission speed | 500 kbps |
Transmission physics | Copper | ID code (dec.) | 127 |
ID code (hex) | 2F | Length code (hex) | 02 |
Length code (dec) | 02 | Process data channel | 32 bit |
Input address area | 4 Byte | Output address area | 4 Byte |
Register length | 32 bit | Required parameter data | 6 Byte |
Required configuration data | 4 Byte | Input name | Analog UTH inputs |
Description of the input | Inputs for thermocouples or linear voltage | Number of inputs | 2 |
Connection method | Spring-cage connection | Connection technology | 2-conductor (shielded) |
A/D conversion time | < 120 µs (per channel) | A/D converter resolution | 16 bit |
Sensor types that can be used (TC) | U, T, L, J, E, K, N, S, R, B, C, W, HK | Measuring principle | Successive approximation |
Measured value representation | 16 bits two's complement and other | Process data update | 30 ms (For both channels) |
Product type | I/O component | Type | modular
Inline |
Operating mode | Process data operation with 2 words | Supply voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 60 mA
typ. 43 mA | Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 18 mA
typ. 11 mA |
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min | Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics) | 500 V AC, 50 Hz, 1 min |
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min | Test voltage: 24 V analog supply (analog I/O)/functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min | Connection name | Inline connector |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Ambient temperature (operation) | -25 °C ... 55 °C | Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice