Product Model
IB IL TEMP 4/8 RTD-EF-XC-PAC

Selling Points
- 1High-precision temperature measurement: Supports all common platinum sensors in accordance with DIN EN 60751 and SAMA.
- 2Multi-sensor compatibility: Compatible with nickel sensors in accordance with DIN 43760, Cu10, Cu50, Cu53, KTY81, and KTY84 sensors.
- 3Advanced communication: Communication via parameter channel (PCP) or four process data words for high-resolution temperature measurement.
- 4Robust design: IP20 degree of protection, suitable for harsh industrial environments.
- 5Easy parameterization: Channels can be parameterized independently via the bus system, including open-circuit detection sensitivity.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 48.8 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on dimensions | Housing dimensions |
Note on application | Only for industrial use | Number of interfaces | 2 |
Connection method | Inline data jumper | Transmission speed | 500 kbps |
Transmission physics | Copper | ID code (dec.) | 223 |
ID code (hex) | DF | Length code (hex) | 05 |
Length code (dec) | 05 | Process data channel | 80 bit |
Input address area | 10 Byte | Output address area | 10 Byte |
Register length | 96 bit | Required parameter data | 31 Byte |
Required configuration data | 5 Byte | Input name | Analog RTD inputs |
Description of the input | Input for resistive temperature sensors | Number of inputs | 8 (for resistance temperature detectors) |
Connection method | Spring-cage connection | Connection technology | 4-conductor |
Note regarding the connection technology | shielded | A/D converter resolution | 24 bit |
Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors, linear resistors | Data formats | IB IL, S7-compatible |
Measuring principle | Sigma/Delta process | Measured value representation | 16 bits (15 bits + sign bit) |
Input filter time | 100 ms
120 ms
200 ms
480 ms (adjustable) | Differential non-linearity | typ. 1 ppm / ±0.0001 % (in all ranges) |
Integral non-linearity | typ. 30 ppm / ±0.003 % (Pt 100)
typ. 20 ppm / ±0.002 % (R
typ. 200 ppm / ±0.02 % (R | Linear resistance measuring range | 0 Ω ... 500 Ω
0 Ω ... 5 kΩ
0 Ω ... 30 kΩ |
Process data update | 1.8 s (Up to 3.3 s possible depending on operating mode) | Product type | I/O component |
Product family | Inline | Type | modular |
Scope of delivery | including Inline connectors and marking fields | Operating mode | Process data mode with 5 words/1 word PCP |
Special properties | Extreme conditions version | Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler
Failure of or insufficient communications power U
User error Error message in the process data |
Article revision | 02 | Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) | Supply voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 120 mA
typ. 95 mA | Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 15 mA
typ. 6 mA |
Test voltage: 7.5 V supply (bus logic), 24 V supply U | 500 V AC, 50 Hz, 1 min | Test voltage: 7.5 V supply (bus logic), 24 V supply U | 500 V AC, 50 Hz, 1 min |
Test voltage: I/O/functional ground | 500 V AC, 50 Hz, 1 min | Connection name | Inline connector |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Ambient temperature (operation) | -25 °C ... 60 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) | Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice