Product Model

IB IL TEMP 4/8 RTD-PAC

In Stock
Last updated: 2025/4/18
Phoenix Contact IB IL TEMP 4/8 RTD-PAC

Selling Points

  • 1Accurate Temperature Measurement: Measures temperature through resistive temperature detectors (RTDs) with high precision.
  • 2Robust Design: Engineered for harsh industrial environments with electromagnetic interference protection.
  • 3Versatile Connectivity: Supports 2- and 3-conductor connection technology for various sensor types (Pt, Ni, Cu, KTY).
  • 4Easy Installation: Includes accessories like connectors and marking fields for straightforward setup.
  • 5Real-Time Data: Provides measured values in milliseconds with diagnostic and status indicators for efficient monitoring.
Product Details
IB IL TEMP 4/8 RTD-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
136.8 mm
Depth
71.5 mm
Note on application
Only for industrial use
Connection method
Inline data jumper
Transmission speed
500 kbps
Transmission physics
Copper
ID code (dec.)
223
ID code (hex)
DF
Length code (hex)
05
Length code (dec)
05
Process data channel
80 bit
Input address area
10 Byte
Output address area
10 Byte
Register length
96 bit
Required parameter data
31 Byte
Required configuration data
5 Byte
Input name
Analog RTD inputs
Description of the input
Input for resistive temperature sensors
Number of inputs
8
Connection method
Spring-cage connection
Connection technology
2, 3-conductor
A/D conversion time
max. 10 µs
Sensor types (RTD) that can be used
Pt, Ni, KTY, Cu sensors, linear resistors
Data formats
IB IL, IB ST, S7 compatible
Measuring principle
Successive approximation
Measured value representation
16 bits (15 bits + sign bit)
Linear resistance measuring range
0 Ω ... 400 Ω 0 Ω ... 20 kΩ
Process data update
6 ms (Up to 230 ms possible depending on operating mode)
Product type
I/O component
Product family
Inline
Type
modular
Scope of delivery
including Inline connectors and marking fields
Operating mode
Process data mode with 5 words/1 word PCP
Article revision
07
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
1.4 W
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 100 mA typ. 75 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 55 mA typ. 28 mA
Test voltage: 7.5 V supply (bus logic)/±15.5 V, ±5 V analog supply (analog I/O)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logic)/functional ground
500 V AC, 50 Hz, 1 min
Test voltage: ±15.5 V, ±5 V analog supply (analog I/O)/functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice