Product Model
IB IL TEMPCON 300 RTD-PAC

Selling Points
- 1The IB IL TEMPCON 300 RTD-PAC offers precise temperature measurement with a resolution of 0.1 K.
- 2Equipped with 6 resistance thermometer inputs and 6 binary outputs for comprehensive control.
- 3Can be extended to 30 control circuits using additional temperature measurement terminals.
- 4Designed for harsh industrial environments with IP20 protection and robust electrical isolation.
- 5Features a transmission speed of 500 kbps for efficient data transfer.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 48.8 mm | Height | 136.8 mm |
Depth | 71.5 mm | Connection method | Inline data jumper |
Transmission speed | 500 kbps | Connection method | V.24 |
ID code (dec.) | 221 | ID code (hex) | DD |
Length code (hex) | 06 | Length code (dec) | 06 |
Process data channel | 32 bit | Input address area | 4 Byte |
Output address area | 4 Byte | Register length | 96 bit |
Required parameter data | 1 Byte | Required configuration data | 5 Byte |
Output voltage | 24 V DC | Output current | 70 mA (short-circuit-proof) |
Product type | I/O component | Product family | Inline |
Type | modular | No. of channels | 6 |
Number of plugs | 4 | Test section | 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
Analog inputs/functional ground 500 V AC 50 Hz 1 min |
Supply voltage | 24 V DC | Max. current consumption | 600 mA |
Typical current consumption | 90 mA | Connection name | Inline connector |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Connection method | Spring-cage connection | Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Degree of protection | IP20 | Ambient temperature (operation) | 0 °C ... 55 °C |
Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (operation) | 75% average, 85% seldom |
Permissible humidity (storage/transport) | 75% average, 85% seldom | Mounting type | DIN rail mounting |