Product Model
IBS IL 24 BK DIO 16/16

Selling Points
- 116 Digital Inputs and Outputs: Handle up to 16 digital inputs and outputs for seamless data transmission.
- 224 V DC Operation: Compatible with 24 V DC power supply for reliable operation in various industrial settings.
- 3500 kbps Transmission Speed: Ensure fast and efficient data transfer with a transmission speed of 500 kbps.
- 4Robust and Durable Design: Built with high-quality materials for long-lasting performance in demanding industrial environments.
- 5Easy Installation and Configuration: Simplify your setup with easy-to-use connectors and diagnostic indicators for quick troubleshooting.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 146.4 mm | Height | 140.5 mm |
Depth | 71.5 mm | Note on application | Only for industrial use |
EMC note | EMC: class A product, see manufacturer's declaration in the download area | Number of interfaces | 2 |
Connection method | Inline shield connector | Transmission speed | 500 kbps |
Number of interfaces | 1 | Connection method | Inline data jumper |
Transmission speed | 500 kbps | Number of local bus devices that can be connected | 63 (observe total permissible current consumption) |
Number of devices with parameter channel | 16 | Number of supported branch terminals with remote bus branch | max. 15 |
ID code (hex) | 4 | Register length | 32 bit |
Input name | Digital inputs | Description of the input | EN 61131-2 type 1 |
Number of inputs | 16 | Connection method | Spring-cage connection |
Connection technology | 3-conductor | Input voltage | 24 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC | Nominal input voltage U | 24 V DC |
Typical input current per channel | typ. 3 mA | Protective circuit | Polarity reversal; Suppressor diode |
Output name | Digital outputs | Connection method | Spring-cage connection |
Connection technology | 3-conductor | Number of outputs | 16 |
Protective circuit | Short-circuit and overload protection; Free running circuit | Output voltage | 24 V DC -1 V (At nominal current) |
Maximum output current per module | max. 8 A | Nominal output voltage | 24 V DC |
Nominal load, inductive | 12 VA | Nominal load, lamp | 12 W |
Nominal load, ohmic | 12 W | Product type | I/O component |
Product family | Inline | Type | modular |
Scope of delivery | including Inline connectors and marking fields | No. of channels | 32 |
Maximum power dissipation for nominal condition | 8 W | Protective circuit | Reverse polarity protection |
Supply voltage | 24 V DC (via Inline connector) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 1.25 A (with max. number of connected I/O terminal blocks (24 V DC supply))
typ. 100 mA (without connected Inline I/O terminals) | Supply voltage | 7.5 V DC ±5 % |
Supply voltage | 24 V DC | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Supply voltage | 24 V DC | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Supply voltage | 24 V DC (via voltage jumper) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Test voltage: 5 V supply, incoming remote bus / 5 V supply outgoing remote bus | 500 V AC, 50 Hz, 1 min | Test voltage: 5 V supply incoming remote bus / 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply | 500 V AC, 50 Hz, 1 min |
Test voltage: 5 V supply, incoming remote bus / 24 V main supply, 24 V segment supply | 500 V AC, 50 Hz, 1 min | Test voltage: 5 V supply incoming remote bus / functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: 5 V supply outgoing remote bus / communications power (U | 500 V AC, 50 Hz, 1 min | Test voltage: 5 V supply outgoing remote bus / I/O (U | 500 V AC, 50 Hz, 1 min |
Test voltage: 5 V supply outgoing remote bus / functional ground | 500 V AC, 50 Hz, 1 min | Test voltage: 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply/functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: 7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply / 24 V main supply, 24 V segment supply | 500 V AC, 50 Hz, 1 min | Test voltage: 24 V main supply, 24 V segment supply/functional ground | 500 V AC, 50 Hz, 1 min |
Connection name | Inline connector | Connection method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Connection method | Spring-cage connection | Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Ambient temperature (operation) | -25 °C ... 55 °C |
Degree of protection | IP20 | Air pressure (operation) | 80 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Permissible humidity (operation) | 95 % (non-condensing) |
Permissible humidity (storage/transport) | 95 % (non-condensing) | Mounting type | DIN rail mounting |
Specifications may be subject to change without notice